CRS 40 V2
Installation, operation and service manual
M2019/02a
Load new base paln
Using base of plan (files BPH and BPL) enable easier orientation in reports and error logs. Not only serial
number of device but also text description of its location is mentioned. Using base of plan is optional, but
without it only serial numbers without description will be used. To load base of plan files .BPH and .BPL must
be packed in .ZIP archive without any directory structure, files of current base of plan will be deleted.
Load new reading plan
Reading plan (list of read devices) is essential for functionality of the system. Reading plan is required for
comparing of planned situation (i.e. installed devices) with really detected devices. It is absolutely necessary
to use up-to-date reading plan. If you change some device, etc., you have to make and load a new reading
plan. To load a reading plan, file(s) .PL must be packed in .ZIP archive without any directory structure, file(s)
of current reading plan will be deleted. System is restarted every time when reading plan is loaded. After
restart, availability of devices are controlled again (like during installation).
Load new authorization keys
Authorization keys are necessary for decoding consumptions. In case of unit replacement, it is therefore
necessary to upload new authorization keys. To load authorization keys, .AUTH file (s) must be packaged in
a .ZIP file without a directory structure.
Files of existing authorization keys will be deleted when
uploading new files!
After the authorization keys are uploaded, the system will be restarted. After restarting
the system, unit availability check is performed (like during installation).
If in a reading plan are units which do not have loaded authorization keys, it is then displayed as reading
units without authorization key: number. Click to see list of units with missing authorization keys.
.AUTH files can be found on the APATOR METRA website authdata.metra-su.cz. In case of troubles, please
contact us.
47 / 57
Illustration 11: Other settings of the reading network