background image

Revision 1.2 

10/2021 

 

Document No. D150-011

 

 

 

 

 

 

Page 

3

 of 

4

 

 
If  the  LED  is 

green  (solid)

,  then  the  module  has  booted  and  is  running 

correctly 

with

 application configuration loaded. 

A / B 

The Ethernet LED will light up when an Ethernet link has been detected (by 
plugging in a connected Ethernet cable). The LED will flash every time traffic 
is  detected.  This  module  has  two  Ethernet  ports  A  and  B.  Each  LEDs 
represents each specific port. 

Run 

The module Run LED will provide information regarding the operational state 
of the CANopen network.  

Solid Green

 

 CANopen network is operational 

Flashing Green

 

 CANopen network is pre-operational 

Blink Green

 

 CANopen network is stopped 

Err 

The Err LED will provide information regarding the operational condition of 
the CANopen devices. 
 

CANopen Master  
Solid Red

 

 No configuration has been loaded on the CANopen Router. 

Flashing  Red

 

  The  primary  interface  (EtherNet/IP  or  Modbus  TCP)  to  the 

CANopen Router has been lost. 

Blink Red

 

 There is an issue with at least one CANopen Slave device. 

Off

 

 There are no issues. 

 

CANopen Slave 
Solid Red

 

 No configuration has been loaded on the CANopen Router. 

Flashing  Red

 

  The  primary  interface  (EtherNet/IP  or  Modbus  TCP)  to  the 

CANopen Router has been lost. 

Blink Red

 

 There is an issue with at least one PDO in the CANopen Router 

when operating as a CANopen Slave device. 

Off

 

 There are no issues. 

Act 

The activity LED is used for the external interface update. Every time there is 
a successful packet received from the external interface (e.g. EtherNet/IP or 
Modbus) the LED will flash green. The LED will flash red if there was an error 
with the received external interface packet (e.g., Checksum error). 

 

CANOPEN TERMINATION 

All  CANopen  networks  need  to  be  terminated  at  the  extremities  (start  and  end  point)  of  the 
communication conductor. The termination for the CANopen network can be enabled/disabled via 
the module configuration. Enabling the termination will connect an internal 120 Ohm resistor across 
the positive (+) and negative (-) conductors of the CANopen network. 
 

ELECTRICAL AND ENVIRONMENTAL 

Specification 

Rating 

Power requirements 

Input: 10 

 32V DC, 

Power consumption 

1.8 W (Max.) 
Current: 155 mA @ 12 V   
Current: 65 mA @ 24 V   

Temperature 

-20 

 70 °C 

 