APAR AR915 Скачать руководство пользователя страница 7

-6 -

 

 

Table 1.Configuration parameters

 

 

Parameter name change - 

 or 

 

Parameter name readout/saving - 
SET, 
Parameter value change - 

 or 

 

Settings 

No. 

Name 

Description of parameter 

Parameter value and range of 
variability 

default 

user’s 

StYP 

type of 
sensor 
(input and 
output) 

RTD 

Pt

= Pt100, 

ni

= Ni100 

Pt 

 

Resistance 

rES

= 10÷540 

-IN or 0÷3200 

 

(max)-OUT 

Thermocouple 

tc-J

=J, 

tc-K

= K, 

tc-S

= S, 

tc-b

B, 

tc-r

= R, 

tc-t

= T, 

tc-E

= E, 

tc-n

= N 

Voltage 

u55

= -5÷55 mV 

rrtd 

total resistance of 2 lines for 
the input 

Pt

ni

 and 

rES

 

0.0

÷ 

50.00 

 (line resistance 

compensation for a 2-wire 
connection in measurements 

0.00

 

 

 

cJtY 

type of compensation of 
temperature of cold tips 

Auto

= automatic, 

conS

= constant 

(defined by parameter 3: 

cJtE

Auto 

 

cJtE 

temperature of cold tips 

0.0

÷ 

50.0

°C (applies to 

thermocouples for 

cJtY

conS

25.0

 °C 

 

ModE 

calibrator operation mode 

in

= measurement (input),  

out

= simulation (output) 

in 

 

FiLt 

filtration rate 

(1)

 

4

÷ 

15

 

 

dot 

resolution of indications 

(2)

 

0

= 1 °C, 

1

= 0.1 °C 

1

= 0.1 °C 

 

LiLo 

lower setting limit for 

SEt

 

/00.0

 ÷ 

3200

 

/00.0 

°C 

 

LiHi 

upper setting limit for 

SEt

 

/00.0

 ÷ 

3200

 

3200

 

 

StEP 

value change step 

SEt

 

0.5

÷ 

200.0

 

1.0

°C 

 

10 

SEt

 

set value 

in the range of the sensor or 

LiLo

÷ 

LiHi

 

100.0

 °C 

 

11 

cALo 

zero point offset 

-50.0

÷ 

50.0

°C 

0.0

 °C 

 

12 

cALG 

gain (sensitivity) 

-85.0

÷ 

115.0

%, 

100.0

 % 

 

13 

bLoc 

keyboard keys lock INOUT 
and 10:

SET

 

oFF

= no lock, 

inou

= lock IN and 

OUT 

SEt

= lock SET

ALL

= lock IN,OUT

SEt

 

oFF 

 

14 

PASS 

password 

(3)

 

0

÷ 

9999

 

1111 

 

15 

Prot 

password protection 

(3)

 

oFF

= off, 

on

= on 

oFF 

 

16 

toFF 

auto-off delay 

(4)

 

0

÷ 

240 

min (

0

- function not active) 

 

Notes: 

(1) 

-  

for 

FiLt

=4 the response time is approx.0.7 s, for 

FiLt

=15 - approx. 2.3 s. A higher filtration 

rate means a smoother measurement value and a longer response time. The parameter 
also applies to measurements of the current polarizing the (thermo)resistance output (in the 
simulation mode). 

(2) 

- does not apply to the resistance sensor (

StYP

=

rES

) and the voltage sensor (

StYP

=

u55

for which the resolution is equal to, respectively:0.1

Ω 

and 0.01 mV, 

(3) 

- when 

Prot

=

oFF

, access to the parameter configuration does not require a password, 

(4) 

- this is the time from the last use of any button 

 
 
 
 
 

Содержание AR915

Страница 1: ...S OFFICE 05 090 Raszyn ul Gałczyńskiego 6 Tel 48 22 853 48 56 48 22 853 49 30 48 22 101 27 31 E mail automatyka apar pl Website www apar pl USER INSTRUCTION TEMPERATURE CALIBRATOR AR915 Version 1 1 0 2015 06 12 ...

Страница 2: ...NCIPLES OF SAFE USE 2 2 GENERAL CHARACTERISTICS OF THE CALIBRATOR 2 3 TECHNICAL DATA 3 4 DIMENSIONS OF THE HOUSING AND DESCRIPTION OF CONNECTIONS AND EXTERNAL ELEMENTS 4 5 BUTTON FUNCTIONS 5 6 PROGRAMMING OF CONFIGURATION PARAMETERS 5 7 SETTING OUTPUT SIGNAL VALUES 7 8 LIST OF MESSAGES AND ERRORS 7 9 USER S NOTES 7 Please pay particular attention to the text marked with this sign The manufacturer ...

Страница 3: ...d a functional keyboard battery 2 x 1 5 V or rechargeable battery 2 x 1 2 V NiMH power supply AA type long operation on a fully charged set of batteries automatic power supply cutoff at low battery charging level automatic shutdown after a preset idle time possibility to test measurement devices and temperature sensors diagnostic functions facilitating detections such defects in tested circuits as...

Страница 4: ...nsor range 1 digit setting simulation Pt100 Ni100 2 C for Ip 200 µA and 3 C for Ip 200 µA J K E N 55 mV 0 3 2 kΩ 0 2 for sensor range and 1 5 Ωfor 0 3 2 kΩ S B R T 0 3 of sensor range Additional error for setting Pt100 Ni100 0 3 2kΩ 2 5 C or 1Ω nonlinearity Additional error for thermocouple inputs 2 C present only in automatic compensation of cold tip temperature Additional error from temperature ...

Страница 5: ...100 Ni100 termin als description 1 2 3 input Pt100 Ni100 Pt500 Pt1000 resistance 3 wire 1 3 input Pt100 Ni100 Pt500 Pt1000 resistance 2 wire 2 3 thermocouple input J K S B R T E N and 0 55 mV OUTPUT OUT Ip Pt100 Ni100 Ω TC mV termin als description 1 3 output Pt100 Ni100 resistance 1Ω 3 thermocouple output J K S B R T E N and 0 55 mV Ip resistance output polarizing current in simulations BATTERY I...

Страница 6: ...of detected connection for a resistance sensor 2 and 3 wire in measurements reference joint temperature for a thermocouple sensor in simulations and in measurements shows the calibrator software version 6 PROGRAMMING OF CONFIGURATION PARAMETERS press the CONF button until approx 2 s the display shows the following temporary message ConF or CodE if password protection is set i e parameter 15 Prot o...

Страница 7: ... 1 C 1 0 1 C 7 LiLo lower setting limit for SEt 00 0 3200 00 0 C 8 LiHi upper setting limit for SEt 00 0 3200 3200 9 StEP value change step SEt 0 5 200 0 1 0 C 10 SEt set value in the range of the sensor or LiLo LiHi 100 0 C 11 cALo zero point offset 50 0 50 0 C 0 0 C 12 cALG gain sensitivity 85 0 115 0 100 0 13 bLoc keyboard keys lock IN OUT and 10 SET oFF no lock inou lock IN and OUT SEt lock SE...

Страница 8: ...e display the lower limit of the sensor range is exceeded or the sensor is defective ConF the parameter configuration mode is entered CodE the mode for entering the password for access to the configuration parameters is entered Err an incorrect password for access to the configuration parameters was entered initiation of the operating mode input output E iH the value of the current polarizing the ...

Страница 9: ... 8 ...

Отзывы: