16
the PID and software
algorithm for the given
output (1/2/3)
10:
SpSt
start/stop of outputs 1/2/3
with function 9:
cLEA
,
messages
Star
/
StoP
/
cLEA
when power is on, default stop
11:
StSP
default start (only for
[F]
and
[SET]
)
67:
HSEt
control signal
setpoint (MV) for outputs
in manual mode
0
÷
100
%
applies to all outputs (1, 2, 3 and analog one),
100
% means the
maximum available output power (set with parameters 13/20/27:
oPF1
/
2
/
3
), step by 1%
(4)
50.0
%
68:
bSEt
Lock of quick
setpoint changes
SEt1
/
2
/
3
, (
chapter 9.1
)
0:
oFF
=
no locks, 1/2/3:
SEt1
/
2
/
3
=
lock of one of the settings
(
SEt1
/
2
/
3
),
4:
SE12
=
simultaneous for
SEt1
and
SEt2
, 5:
SE13
=
for
SEt1
and
SEt3
,
6:
SE23
=
for
SEt2
and
SEt3
, 7:
ALL
=
for
all settings (
SEt1
,
SEt2
and
SEt3
)
oFF
69:
PPro
protection of
configuration with an
access password
0:
oFF
=
entering the
manual
and
remote configuration menu
is not
protected with a password, 1:
on
=
manual
and
remote configuration
(only
for
ARSOFT-CFG) is
protected
with password
on
70:
PASS
access password
0000
÷
9999
password
for entering
the
configuration menu
and for the
MQTT (
chapter 11.1
)
1111
VII. DISPLAY OPTIONS
, submenu
diSP
71:
briG
brightness
10
÷
100
%
display brightness, step by 10%
100
%
72:
wnit
display unit of
measurement
0:
nonE
= none, 1:
M
=m, 2:
ma
= mA, 3:
A
= A, 4:
mW
= mV, 5:
W
= V, 6:
o
C
=°C, 7:
PrH
=
%RH, 8:
PErc
=%, only for AR632.B/652.B/682.B: 9:
k
=
k, 10:
Pa
= Pa, 11:
kPa
=
kPa
o
C
73:
dibo
displayed value
for the bottom line
0:
oFF
= none, 1/2/3:
con1
/
2
/
3
=setpoint
for
output
1/2/3, 4/5/6:
bar1
/
2
/
3
=
MV1/2/3 bargraph
(
output 1/2/3 MV control signal
in the
range
0÷100%), 7:
barA
= bargraph
for
mA/V output, 8:
barP
=
PV bargraph
(measurement
in the
range
:
irLo
÷ 5:
irHi
)
con1
VIII. COMMUNICATION OPTIONS FOR RS485 AND ETHERNET
, submenu
trAn
, description in
chapters 11 ÷ 11.5
74:
r4br
speed for RS485
bitrate kbit/s, 0:
2.4
, 1:
4.8
, 2:
9.6
, 3:
19.2
, 4:
38.4
, 5:
57.6
, 6:
115.2
19.2
kbit /
s
75:
r4cF
RS485 character
format
selection of parity and stop bits, 0:
8N1
(none), 1:
8E1
(even), 2:
8o1
(odd),
3:
8N2
8N1
76:
Addr
MODBUS-RTU
address
1
÷
247
device address
for
RS485
and
suffix
(suffix)
for the
name,
(5)
1
77:
EtMo
Ethernet interface
operating mode
(MAC
hardware
address
available
from
ARSOFT-CFG and
MODBUS-RTU/TCP)
0:
oFF
Ethernet always off (recommended when not in use)
oFF
1:
Auto
DHCP client enabled, network parameters
(from 78:
EIP3
to 89:
EGA0
,
i.e. device IP address, mask and gateway) are set automatically
2:
StAt
DHCP client disabled, network parameters are set manually
78÷81:
EIP3
/
2
/
1
/
0
IP
address
0
÷
255
device's IPv4 address in the local network (Ethernet), 4
consecutive octets
192
.
168
.
0
.
200
82÷85:
ESu3
/
2
/
1
/
0
IP mask
0
÷
255
mask of the IPv4 address in the local network (Ethernet), 4
consecutive octets
255
.
255
.
255
.
0
86÷89:
EGA3
/
2
/
1
/
0
IP
gateway
0
÷
255
router's IPv4 address in the local network (Ethernet), 4
consecutive octets
192
.
168
.
0
.
1
90:
EtcP
MODBUS-TCP
port
1
÷
999
9
TCP port number for the MODBUS-TCP protocol (also for ARSOFT-
CFG)
502
91:
MqMo
operating mode
and type of published
MQTT messages (Ethernet)
(detailed description of
MQTT communication,
chapter 11.1
)
0:
oFF
MQTT protocol disabled (recommended when not used)
oFF
1:
PW
MQTT protocol enabled, only measurement (PV) in the publication,
e.g. "
4.5
"
2:
PWun
MQTT protocol enabled, measurement (PV) and unit in the
publication
3:
nAPW
MQTT enabled, device name, PV and unit in text,
(5)