9. RF Module Option
34
PNEG-2340
Feed-Link 2
Connect Wires to a Network Master
Connect the power cable to “24 VDC” terminal strip on the back right hand side of the Network Master.
Connect the white wire from the power cable to the terminal marked “24 VDC +”. Connect the black wire
to the terminal marked “24 VDC -”. Connect RS485 communication cable to “RS485” out terminal strip on
the black center of the Network Master. Connect the white wire from RS485 cable to the terminal marked
“A”. Connect the black wire to the terminal marked “B”. Connect GND (shield) wire to the terminal marked
“Shield”.
The RF module that is connected to the Network Master either directly or in the daisy chain is considered
the “Server”, so dip switch 6 on the left bank should be ON. All RF modules are setup as “Client” out of the
box. This default setup has dip switch 6 on the left bank in the OFF position and is used for the remote bins.
Figure 9D Network Master and RF Module Wiring Diagram