AnyWireASLINK
4-8
Electric wiring example
Type
Image
Specifications
300V vinyl
cabtyre cable
(VCTF)
JIS C3306
Cross-section area: 0.75mm
2
Allowable current: 7A (30ºC)
Conductor resistance: 25.1Ω/km
(20ºC) or less
Insulation resistance: 5M
Ω/km
(20ºC) or more
Dedicated flat cable
(HKV)
Model: FK4-075-100
(100m winding)
Cross-section area: 0.75mm
2
Allowable current: 7A
Maximum conductor resistance:
25Ω/km
Dedicated flat cable
(HKV)
Model: FK4-125-100
(100m winding)
Cross-section area: 1.25mm
2
Allowable current: 12.7A
Maximum conductor resistance:
15Ω/km
4.7 Transmission line supply current value
The AnyWireASLINK system can be constructed with two wires.
Transmission signals as well as power for the slave unit and whatever is connected to the load side of the
slave unit are superimposed on these two wires.
The allowable supply current (transmission line supply current value) from the transmission line varies
depending on wire diameter and total wiring distance. It is therefore necessary that the total consumption
current of the connected DP-DN (consumption current of the slave unit consumption current on the
load side connected to the two-wire type slave) does not exceed this allowable current value.
Transmission line supply current value
Length of transmission line
Wire diameter of transmission line (DP-DN)
1.25mm
2
0.75mm
2
0.5mm
2
Total length: 50m or less
MAX 2.0A
MAX 1.2A
MAX 0.8A
Total length: Over 50m, no longer than 100m
MAX 1.0A
MAX 0.6A
MAX 0.4A
Total length: Over 100m, no longer than 200m
MAX 0.5A
MAX 0.3A
MAX 0.2A