Chapter 4: DESCRIPTION OF CONNECTION
Operating Manual FU3AM-03
Page 19 of 30
X4-7 Set-Actual
OK
X4-8 Ready
X4-9 COM+
Signalling contact (potential-free): set speed achieved
(only in controller mode)
Ready signaling contact (potential-free))
Reference point for X4-8 and X4-7 (potential-free)
Loading capacity of the signaling outputs: 0.2A, 35VDC or 25VAC
X4-10 GND
X4-11 N2
X4-12 N1
Reference mass for X4-11 ... X4-15
Fixed speed N2 or digital set value, Bit 1
Fixed speed N1 or digital set value, Bit 0
With parameter “source set value” -> “analogue”: N1, N2
With parameter “source set value” -> “digital”: SW_0, SW_1
Fixed set values:
With the input signals fixed speed #1 and fixed speed #2, 3 fixed speeds through
binary coding or the analogue set value specification can be selected.
L
OGIC DIAGRAM
:
Fixed speed
N1 Fixed speed N2
Analogue set value
LOW
LOW
Fixed set value n1
HIGH
LOW
Fixed set value n2
LOW
HIGH
Fixed set value n3
HIGH
HIGH
For parameterisation of the fixed set values, see Section.: 6.2.3
Low = 0 ... +2VDC or open
High = +15 ... 30 VDC
X4-13 L/R
X4-14 RF
X4-15 Reset
High: counter-clockwise rotation, Low: clockwise rotation
Controller enable
Low-High-Flank = fault reset
Low = 0 ... +2VDC or open
High = +15 ... 30 VDC
Cable cross section: 0.4 … 1.5 mm2 (AWG 21 … 16) single/fine strand
8mm