CV-98 INERGEN Valve
The CV-98 valve has a ten (10) year warranty. The valve
requires no internal maintenance. The valve is sealed
closed and must not be disassembled. If there is ever a
malfunction of the CV-98 valve, the complete valve must be
sent back to Ansul for warranty replacement. If the exter-
nal seal is broken, the warranty is voided.
NOTE: Use Flexible Discharge Bend, Part No. 427082, when attaching
valve to supply pipe or manifold.
ANSUL and INERGEN are trademarks of Ansul Incorporated or its affiliates.
System Components
UL EX-4510
12-1-01
Page 1-1
Description
The cylinder is factory filled with INERGEN
®
agent. A single
cylinder may be used or multiple cylinders can be manifolded
together to obtain the required quantity of agent for total flood-
ing. The cylinder valve can be actuated electrically, pneumati-
cally, and/or manually with approved valve actuation compo-
nents. All valves are equipped with an anti-recoil feature.
The cylinders are shipped with a maintenance record card
and protective shipping cap attached to the threaded neck
of each cylinder. This cap entirely encloses and protects
the valve while in shipment.
The equivalent length of the valve is equal to 20 ft. (6.1 m)
of 1/2 in. Sch. 40 pipe.
CV-98 Valve / Cylinder Shipping Assembly
Component
Material
Approvals
Cylinder
Steel
Meets DOT
3AA3000
Valve
Brass
Safety Relief Valve
Brass
Valve/Cylinder
UL Listed
Assembly
(EX-4510)
Shipping Cap
Steel
Shipping
Nominal Cylinder
Actual INERGEN
Approximate
Dimension
Dimension
Assembly
Size
Agent Quantity
Weight
A
B
Part No.
ft.3
(m3)
ft.3
m3
lb.
(kg)
in.
(cm)
in.
(cm)
430952
575
(16.3)
572
(16.2)
322
(146)
68.5
(174.0)
11.0
(27.9)
PRESSURE
GAUGE
SAFETY
RELIEF
VALVE
002252
ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411
Form No. F-2001249 © 2001 Ansul Incorporated Litho in U.S.A.
VALVE
HEIGHT TO OUTLET
CENTER
002251
RECORD
TAG
PRESSURE
GAUGE
CYLINDER
SHIPPING CAP
VALVE SHIPPING CAP
B
A
ANSUL
®
®
Содержание INERGEN
Страница 1: ...INERGEN 200 BAR SYSTEMS DESIGN INSTALLATION RECHARGE AND MAINTENANCE MANUAL ANSUL 004439 ...
Страница 115: ...SECTION XI UL EX 4510 12 1 01 Page 11 2 Typical Applications 002203 13 FT 10 FT 20 FT 2 FT 2 FT 2 5 FT 1 FT ...
Страница 116: ...SECTION XI UL EX 4510 12 1 01 Page 11 3 Typical Applications PIPING LAYOUT 006089 ...
Страница 121: ...ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542 Part No 430149 01 2002 Ansul Incorporated Litho in U S A ...