INSTALLING ACCESSORIES (Continued)
Manual Pull Station (Continued)
6. Feed cable through hole in actuator lever and fasten
with cable clamp. See Figure 15.
7. When installing, make certain there is at least 7 in.
(17.8 cm) of free cable between the cable clamp and
the flared end fitting for proper operation of lever. See
Figure 15.
FIGURE 15
002220
8. Remove wire or pin that was used to hold the lever in
place during cable installation. NOTE: Failure to com-
plete this step will cause system to not actuate when
pull station is used.
ELECTRIC PULL STATION TO AUTOPULSE CONTROL
PANEL – The electric pull station must be mounted in an
area where it will not be exposed to physical abuse or a
corrosive environment. The pull station should be mounted
no higher than 60 in. (153 cm) from the floor, or what the
author ity having jur isdiction requires. See ANSUL
AUTOPULSE Installation, Operation, and Maintenance
Manuals, Part Nos. 74255, 77498, 77513, or 69970 for
detailed wiring instructions.
Alarms
Several types of alarms are available for use with the INER-
GEN system. Some require 24 VDC power and others
require 120 VAC. Make certain that the alarm chosen is
compatible with the detection system control panel used.
24 VDC ALARMS – All alarms used with the ANSUL
AUTOPULSE Control system require 24 VDC power. See
the Component Index in the appropr iate ANSUL
AUTOPULSE installation, operation, and maintenance
manual for description of available alarms.
120 VAC ALARMS – This type of alarm bell can only be uti-
lized with an Ansul AUTOMAN II-C release. It can not be
used on an ANSUL AUTOPULSE Control system.
To properly install the 120 VAC alarm, complete the
following:
NOTICE
All wiring installations must comply with
local, state, and federal codes and must
be completed by a licensed electrician.
1. Install the alarm by first selecting a mounting location
and installing a 4 in. octagon or 4 in. square junction
box.
2. Run 1/2 in. conduit from the releasing device to the
junction box.
3. Feed lead-in wires from release and power supply
junction box.
4. Refer to appropriate wiring diagrams and connect
wires in release junction box.
5. Disassemble alarm by removing bolt from face of bell
housing.
6. Connect lead-in wires to leads from rear of alarm
plunger mechanism.
7. Secure alarm plunger mechanism mounting plate to
junction box.
8. Reassemble housing to alarm mechanism.
Pressure Trip
Pressure trips are used to actuate spring loaded or weight-
ed mechanisms generally used to close doors or windows.
The pressure trip should be securely mounted in the appro-
priate location and piped with 1/4 in. actuation piping back
to the release device.
Pressure trips can be piped off the INERGEN SYSTEM
discharge piping, down stream from the orifice union, which
is the preferred method, or if the system is utilizing an
ANSUL AUTOMAN II-C, the pressure trip can be piped off
the actuation line. See Figure 16.
SECTION VI
UL EX-4510 12-1-01 Page 6-16
Installation
CABLE CLAMP
PULL CABLE
PULL
CABLE
CONDUIT
7 IN. (17.8 cm)
MINIMUM
FLARED
END FITTING
TEMPORARILY
PIN OR WIRE
LEVER IN “SET”
POSITION WHILE
INSTALLING
CABLE
CORNER
PULLEY
Содержание INERGEN
Страница 1: ...INERGEN 200 BAR SYSTEMS DESIGN INSTALLATION RECHARGE AND MAINTENANCE MANUAL ANSUL 004439 ...
Страница 115: ...SECTION XI UL EX 4510 12 1 01 Page 11 2 Typical Applications 002203 13 FT 10 FT 20 FT 2 FT 2 FT 2 5 FT 1 FT ...
Страница 116: ...SECTION XI UL EX 4510 12 1 01 Page 11 3 Typical Applications PIPING LAYOUT 006089 ...
Страница 121: ...ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542 Part No 430149 01 2002 Ansul Incorporated Litho in U S A ...