SECTION VIII
UL EX-4510 12-1-01 Page 8-3
Resetting And Recharge
After the cylinder(s) has been secured back in the bracket
and discharge hose(s) have been reconnected (if neces-
sary, reconnect 1/4 in. actuator hose to ball check port) and
wrench tightened, attach the actuator(s) by completing the
following:
1. Make certain HF and booster actuators have been
reset.
2. Attach both booster and HF actuators to top thread of
CV-98 valve. Securely tighten.
MANUAL VALVE ACTUATOR
Before installing manual actuator back onto cylinder valve,
make certain manual actuator is in the “SET” position. On
manual actuator with ring pins, make certain ring pin is in
position and secured with a visual inspection seal.
If the CV-98 manual actuator was used, apply a small
amount of lubricant, such as WD-40, to the pin between the
handle and the body.
RESETTING SELECTOR VALVE
Reset HF actuator and booster actuator by following the
reset instructions in this section.
NOTE: When actuators are removed to be reset, the selec-
tor valve will automatically reset itself.
MANUAL PULL STATION
Reset remote manual pull station by completing the follow-
ing steps:
1. If necessary, remove set screw that is retaining the
break glass rod.
2. If necessary, carefully remove any remaining broken
glass from station.
3. Press and position handle in proper location against
cover and slide the replacement glass break rod, Part
No. 4834, through stud and handle.
4. Tighten set screw into stud.
REPLACE ANSUL AUTOMAN II-C CARTRIDGE
Install new LT-30-R nitrogen cartridge by completing the fol-
lowing steps:
1. Remove shipping cap and weigh replacement cartridge.
Replace if weight is 1/2 ounce (14.2 g), or more, below
weight stamped on cartridge.
2. Make certain release mechanism is cocked and lock pin
is installed. Then, install replacement cartridge into
release assembly and hand tighten.
3. Remove lock pin.
4. Secure cover on ANSUL AUTOMAN II-C release and
seal with visual inspection seal.
5. Record recharge date on tag attached to unit and/or in
a permanent file.
NOTIFY OWNER
1. Notify owner and/or authority having jurisdiction that the
system has been recharged and placed back in service.
CAUTION
!
Make certain all electric power from the panel to the
actuator has been disconnected. Failure to disconnect
power may cause system to accidentally discharge.
Содержание INERGEN
Страница 1: ...INERGEN 200 BAR SYSTEMS DESIGN INSTALLATION RECHARGE AND MAINTENANCE MANUAL ANSUL 004439 ...
Страница 115: ...SECTION XI UL EX 4510 12 1 01 Page 11 2 Typical Applications 002203 13 FT 10 FT 20 FT 2 FT 2 FT 2 5 FT 1 FT ...
Страница 116: ...SECTION XI UL EX 4510 12 1 01 Page 11 3 Typical Applications PIPING LAYOUT 006089 ...
Страница 121: ...ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542 Part No 430149 01 2002 Ansul Incorporated Litho in U S A ...