Main Parts

1

3

8

7

 9

2

5

4

6

1.  Remote Control Connection Port
2.  MicroUSB Port
3.  DC Input Connection: Marathon Power 

Stud Block (1/4” studs)

4.  Chassis Grounding Stud
5.  Indicator LEDs
6.  Lighted ON/OFF button

7.  AC Output Connection: Phoenix 

VDFK4 Terminal Block

8.  AC Output Connection: 5-15 

NEMA Outlet

9.  Thermal Carling 20A  

Circuit Breaker

10. AC Output Connection: 5-15 

NEMA Outlet

Front Panel

1.  Thermostatic Cooling Fan 

Rear Panel (Not Pictutred)

Содержание IPSi2400 Series

Страница 1: ...ies PURE SINE INVERTER 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Страница 2: ...oving this device Medical Equipment Notice Analytic Systems does not recommend the use of their products in life support applications where failure or malfunction of this product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness Analytic Systems does not recommend the use of any of its products in direct patient care Examp...

Страница 3: ...t Warnings and Advisories Table of Contents Introduction Box Contents Main Parts Operation Two Stage Charging Installation Troubleshooting Specifications Warranty Revised September 20 2017 Copyright 2005 2017 Analytic Systems Ware 1993 Ltd ...

Страница 4: ...ls without rewiring Built for the safest operation possible this unit features low voltage warning with shutdown circuitry to protect the DC power source While the Inverter is safeguarded by high voltage and over temperature protection both with shutdown circuitry All the alarm conditions can be monitored on the bright LED indicator display which can also be mirrored on the optional remote control...

Страница 5: ...tud Block 1 4 studs 4 Chassis Grounding Stud 5 Indicator LEDs 6 Lighted ON OFF button 7 AC Output Connection Phoenix VDFK4 Terminal Block 8 AC Output Connection 5 15 NEMA Outlet 9 Thermal Carling 20A Circuit Breaker 10 AC Output Connection 5 15 NEMA Outlet Front Panel 1 Thermostatic Cooling Fan Rear Panel Not Pictutred ...

Страница 6: ...LED and On Off button will stop glowing High Voltage The LED blinks red when the input voltage nears the maximum limit for proper operation It glows red when the input voltage is too high for proper operation The Bypass LED will also glow red and the Invert LED and On Off button will stop glowing Over Temp This LED blinks red if the unit s internal temperature nears the safe limit The Inverter wil...

Страница 7: ...bility of it generating any radio frequency interference The unit case must be bonded appropriately to the grounding system of the vehicle or marine vessel On a vehicle bond the case to the vehicle s frame On a marine vessel bond the case to the vessel s hull A grounding stud is provided on the front panel for this purpose To ensure proper grounding check the connection with an ohmmeter The case i...

Страница 8: ...rminal block stud s using RED AWG12 stranded wire and appropriately sized lugs Connect the negative terminal of the DC power source to the indicated terminal block stud s using BLACK AWG12 stranded wire and appropriately sized lugs TIP Use the largest gauge AWG 1 0 recommended and shortest length of welding wire possible The biggest effect on Inverter performance and EMI is the length and gauge of...

Страница 9: ...o provided for wiring to a distribution panel It is wired as follows CAUTION Do not apply AC voltage to the output connection This will damage the Inverter and will not be covered under warranty CAUTION This terminal block is NOT protected by a circuit breaker Each device wired to the distribution panel connected to the terminal block must have its own circuit breaker Ensure that the total average...

Страница 10: ... RS232 6 Green Gnd RS232 7 White Brown Dry Contact Relay 8 Brown Dry Contact Relay Remote On Off Pins 1 White Orange and 2 Orange can be used to turn the Inverter ON or OFF Connect the pins together through a switch or relay to turn the Inverter OFF and disconnect them to turn the Inverter ON The front panel power switch must be ON for this connection to function Isolated RS232 Communications Pins...

Страница 11: ...terWizard manual TIP Choose batteries with enough capacity to ensure that the Inverter can power the load for the required amount of time in the event of AC power failure For example a 2000W Inverter running from 24 VDC input will draw 100 amps so for 2 hours of runtime the minimum required battery capacity is 280 amps hours of capacity at 24 volts InverterWizard Program The Inverter is factory pr...

Страница 12: ...unit must be returned for repair HIGH VOLTAGE The input voltage is too high for normal operation Fix Check that the rating of the DC power source is appropriate for the application The Inverter can be damaged if the input voltage exceeds the maximum rating Over voltage damage is not covered under warranty If the power source is functioning correctly the cause is likely an internal component failur...

Страница 13: ...84 US Canada www analyticsystems com info analyticsystems com Revised June 24 2016 Mechanical Length 15 2 in 38 5 cm Width 9 4 in 23 8 cm including lifting handles Height 9 3 in 23 6 cm Clearance 1 in 2 5 cm all around Material Marine Grade Aluminum Finish Black Powder Epoxy Black Anodized Fastenings 18 8 Stainless Steel Weight 52 5 lb 24 0 kg Connections DC In Marathon ST722B2502UH 175 Amp 300V R...

Страница 14: ......

Страница 15: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of th...