Off-line UPS (Optional)

The Off-line UPS (Uninterrupted Power Source) option allows the Inverter to be used as a 

backup power source in the event of external AC power failure.

To set up the Off-line UPS

1.  Connect the external AC power source to the AC Input Connection.

2.  Connect the batteries to the DC Input Connection. 

3.  Connect the load to the AC Output Connection.  

4.  Move the Power Switch to the ON position. The Bypass LED will glow green indicating 

the load is drawing current from the AC Input Connection.

In the event that external AC power fails, the Inverter will sense the voltage drop, power 

on, and begin supplying AC power to the load. It will continue to do so until either time the 

external AC power is restored or the batteries become discharged.  

The voltage thresholds for the Inverter to take over supplying AC Power or to stop supplying 

AC power to the load are all factory-preset to typical values. However, you can use the  

InverterWizard 

software to adjust these values to fit your specific needs. For more information, 

see the 

InverterWizard

 manual. 

TIP:  

Choose batteries with enough capacity to ensure that the Inverter can power 

the load for the required amount of time in the event of AC power failure. 

For example, a 2000W Inverter running from 24 VDC input will draw ~100 amps, so for 2 hours 

of runtime the minimum required battery capacity is 280 amps hours of capacity at 24 volts.

InverterWizard Program

The Inverter is factory preset for the input voltage, output voltage, and output frequency 

on the label. If these parameters are satisfactory, the Inverter can be put immediately into 

service.

The low voltage shutdown parameters are set for the lowest battery voltage that the Inverter 

will support. They are 12 Volts for a -12 model, 24 Volts for a -20 mode, and 48 Volts for a -40 

model

If the Inverter is powered by alternate DC battery voltage such as 32/36 Volts for a -20 model 

or 72 Volts (rail) for a -40 model, then the low voltage shutdown parameters will need to be 

changed. You can do this using the free-to-download 

InverterWizard 

software from  

www.analyticsystems.com

With 

InverterWizard

, you can also:  

•  Set the Output Frequency (50.00 or 60.00 Hz)

•  Adjust the Output Voltage  (

±

10% range at 1 VAC intervals)

•  Set the voltage thresholds for UPS (For units with the Off-line UPS Option) 

Содержание IPSi2400 Series

Страница 1: ...ies PURE SINE INVERTER 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Страница 2: ...oving this device Medical Equipment Notice Analytic Systems does not recommend the use of their products in life support applications where failure or malfunction of this product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness Analytic Systems does not recommend the use of any of its products in direct patient care Examp...

Страница 3: ...t Warnings and Advisories Table of Contents Introduction Box Contents Main Parts Operation Two Stage Charging Installation Troubleshooting Specifications Warranty Revised September 20 2017 Copyright 2005 2017 Analytic Systems Ware 1993 Ltd ...

Страница 4: ...ls without rewiring Built for the safest operation possible this unit features low voltage warning with shutdown circuitry to protect the DC power source While the Inverter is safeguarded by high voltage and over temperature protection both with shutdown circuitry All the alarm conditions can be monitored on the bright LED indicator display which can also be mirrored on the optional remote control...

Страница 5: ...tud Block 1 4 studs 4 Chassis Grounding Stud 5 Indicator LEDs 6 Lighted ON OFF button 7 AC Output Connection Phoenix VDFK4 Terminal Block 8 AC Output Connection 5 15 NEMA Outlet 9 Thermal Carling 20A Circuit Breaker 10 AC Output Connection 5 15 NEMA Outlet Front Panel 1 Thermostatic Cooling Fan Rear Panel Not Pictutred ...

Страница 6: ...LED and On Off button will stop glowing High Voltage The LED blinks red when the input voltage nears the maximum limit for proper operation It glows red when the input voltage is too high for proper operation The Bypass LED will also glow red and the Invert LED and On Off button will stop glowing Over Temp This LED blinks red if the unit s internal temperature nears the safe limit The Inverter wil...

Страница 7: ...bility of it generating any radio frequency interference The unit case must be bonded appropriately to the grounding system of the vehicle or marine vessel On a vehicle bond the case to the vehicle s frame On a marine vessel bond the case to the vessel s hull A grounding stud is provided on the front panel for this purpose To ensure proper grounding check the connection with an ohmmeter The case i...

Страница 8: ...rminal block stud s using RED AWG12 stranded wire and appropriately sized lugs Connect the negative terminal of the DC power source to the indicated terminal block stud s using BLACK AWG12 stranded wire and appropriately sized lugs TIP Use the largest gauge AWG 1 0 recommended and shortest length of welding wire possible The biggest effect on Inverter performance and EMI is the length and gauge of...

Страница 9: ...o provided for wiring to a distribution panel It is wired as follows CAUTION Do not apply AC voltage to the output connection This will damage the Inverter and will not be covered under warranty CAUTION This terminal block is NOT protected by a circuit breaker Each device wired to the distribution panel connected to the terminal block must have its own circuit breaker Ensure that the total average...

Страница 10: ... RS232 6 Green Gnd RS232 7 White Brown Dry Contact Relay 8 Brown Dry Contact Relay Remote On Off Pins 1 White Orange and 2 Orange can be used to turn the Inverter ON or OFF Connect the pins together through a switch or relay to turn the Inverter OFF and disconnect them to turn the Inverter ON The front panel power switch must be ON for this connection to function Isolated RS232 Communications Pins...

Страница 11: ...terWizard manual TIP Choose batteries with enough capacity to ensure that the Inverter can power the load for the required amount of time in the event of AC power failure For example a 2000W Inverter running from 24 VDC input will draw 100 amps so for 2 hours of runtime the minimum required battery capacity is 280 amps hours of capacity at 24 volts InverterWizard Program The Inverter is factory pr...

Страница 12: ...unit must be returned for repair HIGH VOLTAGE The input voltage is too high for normal operation Fix Check that the rating of the DC power source is appropriate for the application The Inverter can be damaged if the input voltage exceeds the maximum rating Over voltage damage is not covered under warranty If the power source is functioning correctly the cause is likely an internal component failur...

Страница 13: ...84 US Canada www analyticsystems com info analyticsystems com Revised June 24 2016 Mechanical Length 15 2 in 38 5 cm Width 9 4 in 23 8 cm including lifting handles Height 9 3 in 23 6 cm Clearance 1 in 2 5 cm all around Material Marine Grade Aluminum Finish Black Powder Epoxy Black Anodized Fastenings 18 8 Stainless Steel Weight 52 5 lb 24 0 kg Connections DC In Marathon ST722B2502UH 175 Amp 300V R...

Страница 14: ......

Страница 15: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of th...

Страница 16: ...ems com support warranty registration DESIGNED AND MANUFACTURED BY 800 668 3884 604 946 9983 sales analyticsystems com www AnalyticSystems com 8128 River Way Delta BC V4G 1K5 Canada Battery Chargers Inverters Power Supplies Voltage Converters ...

Отзывы: