Installation and Operation Manual for
4-20mA RF Wireless Transmitter Model A753
5
Analynk Wireless, LLC
!
790 Cross Pointe Road
!
Columbus, OH 43230
Phone: (614) 755-5091 Fax: (614) 755-5093 Web:
www.analynk.com
Note: b000 is binary 000, the decimal equivalent of decimal 0. The least significant bit
is switch position 3.
Mode 0 (b000): Normal operation
; this mode is for standard 4-20mA and switch
status operation. The unit is normally left in this mode.
Mode 1 (b001): Calibration mode Zero adjust
; See Section 4.3 for Zero/Span Cali-
bration.
Mode 2 (b010): Calibration mode Span adjust
; See Section 4.3 for Zero/Span Cali-
bration.
Mode 3 (b011): RF Channel Select:
Set mode switches for mode 3 (see figure 3) then
press and release the reset switch. There are 8 RF channels available, 0-7. After
power up sequence, the present RF channel will be displayed, see figure 4. To return
to normal mode return all switches to b000 or to change RF, channels press and re-
lease the program switch and the next incremented channel will be displayed. Each
subsequent press and release of the program switch increments the RF channel, chan-
nels will wrap around from 7 to 0. When the desired channel is displayed, press and
hold the program switch for five seconds, the power LED will blink twice to indicate
value has been stored. Return all switches to b000, programming is complete.
The RF
channel must match the RF channel on the receiver.
Refer to A750 Receiver manual
for RF Channel Select procedure.
ON
13
2
0
1
2
3
4
5
6
7
RF CHANNEL
LEDS IN RF
CHANNEL MODE
PROGRAM
RESET
Figure 4 RF Channel Selection.
Mode 4 (b100): RSSI mode:
Set mode switches
for mode 4. In this mode the RF field strength can
be monitored on the model A750 receiver. The
A750 receiver must also be in RSSI mode for
proper operation. Refer to A750 Receiver manual
for RSSI Mode procedure. RSSI Mode can be
helpful during installation for antenna alignment.
Mode 5 (b101): Demo mode
: Set mode switches
for mode 5. All inputs are automatically simulated
in the following sequence: 4.00mA, 20.00mA, A1
closed, A2 closed, 20mA 4.00mA, 20mA, A1
open, A2 open, 20.00mA, and repeat. All input
connections are ignored in this mode. Return all
switches to b000 when demo is complete.