background image

Installation and Operation Manual for  

4-20mA RF Wireless Transmitter Model A753 

Analynk Wireless, LLC 

!

 790 Cross Pointe Road 

!

 Columbus, OH 43230 

Phone: (614) 755-5091 Fax: (614) 755-5093 Web: 

www.analynk.com

 

 

ACCESS

DOOR

TX (TRANSMIT)

RX 
(RECEIVE)

PROGRAM SWITCH

MODE 
SWITCHES

SWITCH STATUS/ALARM 2

SWITCH STATUS/

ALARM 1

RESET

POWER

RF LINK

1

ON

3
2

Figure 2 Access door, switch and LED locations. 

4.0 Setup 

Transmitter setup is accomplished without software. Access the programming but-
tons and switches by lifting the access door as shown in figure 2.    

 
4.1 Power up Sequence  

When the A753 is pow-
ered, LEDs light in the 
following sequence: 
Power, RF Link, A1, A2. 
Then either A1 or A2 will 
blink (4) times – this will 
indicate Normal RF Mode 
or Repeater Mode – see 
Section 4.4 for configura-
tion. After a brief pause 
all LEDs will report the 
appropriate status. 
 

4.2 Mode Switch Selec-
tion  

The mode switches are 
used for calibration, RF 
channel selection and 
RSSI (received signal 
strength indication) activation. Figure 3 shows the function of each switch position.  

 
Return all switches to Mode 0 for normal operation.  Refer to figure 3 for mode 
switch settings. 

 

 

Figure 3 Mode switches. 

MODE

SWITCH POSITIONS

ON

6

7

5

4

2

ON

110

RF POWER USE

FACTORY USE

ON

111

1

1

23

RSSI MODE

DEMO MODE

3
2
1

3

ON

101

ON

100

2
13

3

2

0

1

SPAN ADJUST

RF CHANNEL SELECT

ON

011

2
13

ON

010

2
13

ZERO ADJUST

000

NORMAL

1

ON

001

2
13

ON

23

1

PROGRAM

RESET

MODE SWITCH

2

3

Содержание A753

Страница 1: ...ireless Transmitter Model A753 1 Analynk Wireless LLC 790 Cross Pointe Road Columbus OH 43230 Phone 614 755 5091 Fax 614 755 5093 Web www analynk com Wireless LLC Installation and Operation Manual for 4 20mA RF Wireless Transmitter Model A753 Rev 1 3 ...

Страница 2: ...l installation Designed to interface with A750 re ceiver Demo mode 1 0 Features 2 0 Description The A753 has one 4 20mA input and two discrete inputs Other analog inputs are available always refer the label on the side of the unit to determine proper input Dis crete inputs can be either wet or dry The status of the discrete inputs is displayed on the front panel as A1 and A2 The 4 20mA input signa...

Страница 3: ... INTERNAL TO A753 5 to 32 VDC WET CONTACT S2B GROUND RF TRANSMITTER TX A2 11 A753 SWITCH 1B WET CONTACT SWITCH 2B WET CONTACT 10 7 8 WET CONTACT S1B GROUND 5 to 32 VDC RF LINK A1 PWR RX SWITCH 2A DRY CONTACT 12 9 5Vdc 10K 10K SWITCH 1A DRY CONTACT 4 20mA INPUT 5Vdc 4 5 2 1 DC POWER SUPPLY 11 32 VDC 6 3 Terminal Number Terminal Description Terminal Number Terminal Description 1 Positive 11 to 32 Vd...

Страница 4: ...ing sequence Power RF Link A1 A2 Then either A1 or A2 will blink 4 times this will indicate Normal RF Mode or Repeater Mode see Section 4 4 for configura tion After a brief pause all LEDs will report the appropriate status 4 2 Mode Switch Selec tion The mode switches are used for calibration RF channel selection and RSSI received signal strength indication activation Figure 3 shows the function of...

Страница 5: ...ill be displayed Each subsequent press and release of the program switch increments the RF channel chan nels will wrap around from 7 to 0 When the desired channel is displayed press and hold the program switch for five seconds the power LED will blink twice to indicate value has been stored Return all switches to b000 programming is complete The RF channel must match the RF channel on the receiver...

Страница 6: ...or 4 20mA below as necessary 4 3 1 Lift Access Door to expose mode reset and programming switches see figure 3 4 3 2 Connect calibration source to 4 20ma input see figure 1 and table 1 4 3 3 Set mode switch to Mode 2 Span Adjust see figure 3 for proper setting 4 3 4 Apply power to unit or if unit is already powered press and release the reset switch after unit has completed power up sequence apply...

Страница 7: ...ink 4x at initial power up To program for Normal RF or Repeater mode please do the following 4 4 1 Lift Access Door to expose mode reset and programming switches see figure 2 4 4 2 Press Reset switch and then press hold programming switch 4 4 3 After initial power up the Normal RF Configuration will change from one to the other by blinking the appropriate A1 or A2 LED Release Programming switch 4 ...

Страница 8: ...llation and Operation Manual for 4 20mA RF Wireless Transmitter Model A753 8 Analynk Wireless LLC 790 Cross Pointe Road Columbus OH 43230 Phone 614 755 5091 Fax 614 755 5093 Web www analynk com Wireless LLC ...

Отзывы: