Installation Sheet
RDD-DM6
6-Channel Integrated Dimmer Module 120,240,277 VAC
The RDD-DM6 Six-Channel Integrated Dimmer Module controls up to six
dimmed channels with six onboard 10 A dimmers. The RDD-DM6 is
designed for use with the RDA series of enclosures, in a AMX Lighting™
modular digital dimming system. The RDD-DM6 is controlled by AXlink,
PROlink, or by dry (contact) closures. The RDD-DM6's 120, 240, and 277
VAC ratings are CE, UL, and C-UL approved.
RDD-DM6 UL and C-UL Ratings (per circuit)
Input
•
120, 240, 277 VAC, single phase, 3-wire, 50/60 Hz, 2400 W, one feed
•
120, 240, 277 VAC, single phase, 4-wire, 50/60 Hz, 4800 W, two feed
Output
•
1200 W max. per channel @120, 240, 277 VAC
•
2400 W max. total, all six channels on with 2400 W feed
•
4800 W max. total, all six channels on with dual 2400 W feeds
•
Feed circuit #1 goes to dimmer 1, 3, and 5; feed circuit #2 goes to
dimmer 2, 4 and 6
Suggested Switched Loads
•
Incandescent
•
Low-voltage
•
Neon, cold-cathode
•
Motors
•
Fans
Specifications
•
Dimensions (HW): 5.87" x 10.0" (149.00 mm x 254.00 mm)
•
Use wires rated at 75°C (167°F)
•
Torque terminals to 20 in-lbs (2.3 N/M)
•
Max. wire size: 10 AWG (4 mm²)
•
Wire stripping length: 0.28" (7 mm)
•
Weight: 4.5 lbs (2.04 kg)
•
BTU/hr:
300
single feed (2400 W);
600
dual feed (4800 W)
•
Power consumption: 50 mA @ 120 VAC, 25 mA @ 240 VAC, 22 mA
@ 277 VAC
•
Control port current: 200 mA @ 12 VDC
Caution: Pre-Installation Notes
•
All Class 1 wiring must be connected to proper terminals.
•
All control wiring must be connected to proper terminals.
•
Disconnect power while installing or connecting the unit.
•
Keep top and bottom air vents clear at all times.
•
Test loads for shorts before connecting.
•
Use low-voltage wires with a 300 volt rating or greater.
•
Use field installed copper conductors.
•
All electrical ratings are for continuous duty.
•
For indoor use only.
•
This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting AXlink:
Connect the 4-pin captive-wire AXlink from the RDD-DM6 to the Central
Controller for AXlink control of the dimming system.
Connecting PROlink:
Connect the orange 4-pin captive-wire PROlink connector from the
RDD-DM6 to a PRO-DP8 PROlink wall panel.
Line-in Connections:
FIG. 1
RDD-DM6 6-channel Integrated Dimmer Module
5.87" (149 mm)
Mounting points
Mounting points
Dimmers
Bridge
High
connections
Load out
10.00"
(254.00 mm)
DRY CLOSURES
AXlink connector
PROlink connector
Ex12V power
connector (optional)
Neutral
Chokes
AXlink address
DIP switch
PROlink
DIP switch
RESET
button
MEMORY
PROTECT
jumper
voltage
address
FIG. 2
Connecting AXlink
FIG. 3
Connecting PROlink
FIG. 4
Line-in Connections
PWR
AXP
AXM
GND
PWR
AXP
AXM
GND
Central
RDD-DM6
Controller
(optional)
PRO-DP8
Pack 1
Pack 2
+12
PR+
PR-
GND
+12
PR+
PR-
GND
Dual 2400 W Inputs
Bridged 2400 W Input
20 A
Using two feeds for line 1 and line 2 provides
two, 2400 W inputs.
Bridging line 1 and line 2 provides a single
2400 W input.