Installation
9
Radia Lighting Control System
RDA-ENC6B 120/240 VAC line input (single phase)
FIG. 10 shows a 120/240 VAC single-phase (3 W + G) wiring diagram for the RDA-ENC6B line
input terminal block.
Connecting high-voltage, three-phase input power and loads
Follow these steps to wire high-voltage (120 VAC and 240 VAC), three-phase power connections
(FIG. 11) to any of the AMX Lighting modules.
1.
Connect the green ground wire(s) to the copper ground lug on the enclosure. Ensure the ground
wire is properly connected to earth ground.
2.
Connect the white neutral wire(s) to one of the terminals on the enclosure's neutral terminal
block.
3.
Provide a separate neutral wire for each controlled zone.
4.
Connect the black line input from the electrical panel to the enclosure's line terminal. The line
input terminal accepts a 0 AWG copper conductor.
FIG. 10
RDA-ENC6B 120/240 VAC single-phase (3 W + G) wiring diagram
FIG. 11
High-voltage, three-phase input power
1
2a
2b
3
1
2a
2b
3
RDA-ENC6B
Connect to neutral block
line input terminal
These
connections
are factory-
wired