Temposonics
®
R-Series
V
Analog
Operation Manual
I 58 I
5.4.9 Programming via cabinet programmer
Cabinet programmer for Analog output (part no. 253 408), connect-
ed between sensor and control unit is provided for setup of measuring
range by moving the magnet on desired Null/Span positions (min-
imum distance between setpoints: 25 mm) and pushing the corre-
sponding 0 % respectively 100 % buttons on programmer.
PLC
SENSOR
Program /Run
Start
0 %
100 %
Programming mode
24 VDC
Out 1 / Pin 1, GY
GND 1 / Pin 2, PK
Out 2 / Pin 3, YE
GND 2 / Pin 4, GN
24 VDC / Pin 5, BN
GND / Pin 6, WH
1
2
3
4
5
6
1
2
3
4
5
6
Analog input module
Power supply
Fig. 80: 1-magnet measurement
1 Magnet position
Active measuring range
1 Magnet sensor
Output 1: position
0 %
100 %
2 Magnets
Active measuring range
min. 76 mm
0 %
100 %
2 Magnet sensor
Output1: Position magnet 1, Output 2: Position magnet 2
Fig. 81: Connecting sensor with cabinet programmer
Mounting
The programmer electronics housing is designed for snap-in mounting
on standard 35 mm rails (EN 607 15/50022). It is suitable for con-
nection between sensor and controller in a cabinet. The programming
mode can be activated without any additional service tool at any time.
Normal function:
1. Slide the Program/Run switch to run (all sensor leads are
connected to the controller).
a.) The sensor LED is green to indicate normal function.
Activate the programming mode:
1. Slide the Program/Run switch to program.
a.) Press the Start button and 100% button simultaneously.
Release the Start button first, wait until the sensor's LED
changes from green to flashing blue, then release the 100%
button.
b.) The flashing blue LED indicates that the sensor is now in
command mode.
2. Adjust the position for the start of output,
(0 % = 0 VDC, −10 VDC, 4 mA, or 0 mA).
a.) Move the magnet to the start position.
b.) Press and hold the 0 % button until the flashing blue LED
changes to flashing green, and then release the 0% button.
The LED will then return to flashing blue.
3. Adjust the position for the end of output
(100 % = 10 VDC or 20 mA).
a.) Move the magnet to the end position.
b.) Press and hold the 100% button until the flashing blue
LED changes to flashing green, and then release the 100 %
button. The LED will then return to flashing blue.
4. Save your settings and exit the command mode:
a.) Press and release the Start button. The LED will change from
flashing blue to green on.
b.) Slide the Program/Run switch to run.