PAGE 6
LS4808 / LS4816 | 8 / 16 CHANNEL SPEAKER LINE SURVEILLANCE
1. Setup Menu
BASIC SETUP
There are 2 modes of operation available : Basic and Advance.
In Basic setup mode, LS4808 / 4816 shall detect the circuit for circuit fault automatically. The timing of detection shall
depend on the intervals set in Auto Detection mode, ( Refer to Auto Test section ). Follow the steps below to use this mode.
EXIT
MAIN MENU
ENTER
>
1. SETUP
ENTER
>
CHANNEL 01: IMPEDANCE
MONITORED / BYPASS
ENTER to confirm or press PREV/NEXT button untill EXIT option show up
then press ENTER to EXIT.
>
1. SETUP
1. BASIC SETUP
PREV
>
NEXT
>
CHANNEL 01: IMPEDANCE
MONITORED
CHANNEL 01: IMPEDANCE
BYPASS
Press Next / Prev button to switch the Channel
>
ADVANCE SETUP
EXIT
MAIN MENU
ENTER
>
1. SETUP
ENTER
>
CHANNEL 01: OPEN
MONITORED / BYPASS
ENTER to confirm & press PREV button for EXIT
>
1. SETUP
2. ADVANCE SETUP
PREV
>
NEXT
>
CHANNEL 01: OPEN
MONITORED
CHANNEL 01: OPEN
BYPASS
Press Next / Prev button to switch the Channel
>
CHANNEL 01: OPEN
LOW LIMIT: 0005
Ω
>
CHANNEL 01: OPEN
HIGH LIMIT: 010K
Ω
>
Press Next / Prev button to switch the Channel
On selected set High-limit
On selected set Low-limit
CHANNEL 01: OPEN
MONITORED
>
ENTER
NEXT
>
1. SETUP
2. ADVANCE SETUP
NEXT
>
1. SETUP
3. BUZZER
Note: In long cable circuit or zone with multiple branchings the basic mode may not be suitable to detect the fault such as short
at the far end of cable (e.g: 500m), cables itself has resistance, thereby would not show short phenomena. It is therefore,
Advance setup shall be used.
Refer to
Advanced Setup
Fault Detection: Open : +/- 15% from measured impedance
(to be available)
Press Enter to confirm setting
& Next / Prev button to switch the Channel
Press Enter to allow LS to
perform a impedance limits
calibration. NEXT/PREV button
to switch the channel.
ENTER
Press Enter to confirm setting
& Next / Prev button to switch the
Channel