5.1 LED Indication
On the front facia there are 5 status indication LEDS:
5.1.1 Reset LED
When the STOP button is pressed to stop/lock the UPS, this LED starts flashing and remains flashing
until the UPS is unlocked by pressing the RESET button. The LED remains flashing when the UPS is in
lock mode. The application of mains power while the UPS is locked will not start the UPS; it will be
necessary to press the RESET button to unlock and then press the START button to start the UPS.
5.1.2 Stop LED
When the UPS is unlocked (by pressing the RESET button) it forces the STOP LED to begin flashing.
This means that the UPS is ready to start and pressing and holding the START button for 1-second will
start the UPS. The UPS may also be started by momentarily closing the term
inals ‘Start+’ and ‘Start In’
located at X7 on the terminal Board. The successful start is indicated by the OUTPUT LED becoming
illuminated at which time output will be available at the output terminals. The application of mains power
while the UPS is unlocked will immediately start the UPS.
5.1.3 Output LED
This LED illuminates when the UPS is on.
5.1.4 Overload LED
This LED illuminates when the UPS is operating in current limit mode, and extinguishes when operating
normally.
5.1.5 Mains On LED
This LED illuminates when the mains power is applied to the UPS, and extinguishes when mains power
is switched off.
5.1.6 LCD Backlight
The LCD display turns off 30-second after the last press on any button.
5.2 Battery Life
Provided the ISUPS is stored as per the requirements listed in Section 2, the battery within the unit can
be expected to have an operational lifespan of approximately 3 years at an ambient temperature of 20
˚C.
It is important to note that the ISUPS
’s battery life is a function of temperature, and as such, the
expected life span of the battery must be degraded as the ambient temperature increases. At an ambient
temperature of 40
˚C, the life of the battery within the ISUPS is reduced to approximately 1 year (see
Section 12.3
“Equipment Overhaul”).
CAUTION!
The “Reset” LED flashes continuously (<1-second intervals) to indicate
that this equipment is in “Stand-by” mode and contains an operational
battery pack. The battery life is 12 months for the 300Wh UPS when
stored in the recommended manner.
ENVIRO
Lead-acid batteries are recyclable products. Recognising the need to be
involved in the whole lifecycle of a battery and to protect the
environment, Ampcontrol will recycle batteries from ISUPS units that
are returned to Ampcontrol at the end of their life.