ISUPS2B004 Rev 1
Page 47 of 70
Ampcontrol Pty Ltd
– ABN 28 000 915 542
ISUPS 300Wh V2 USER MANUAL
ISUPS2B004 R2
– DEC/17
10.8 Trip / Reset Latch
– 7
th
Major Sub-Menu
6G. Trp RST Setup
Press the UP button to access this menu. This major sub menu allows the viewing and setting of the trip
reset function. When active, this function allows trips from external devices to be latched.
10.8.1 Enable / Disable Menu
Trp RST Enabled:
> Yes<
Press the RIGHT button to access this menu.
The Enable / Disable menu allows the trip reset latch function to be enabled or disabled. Pressing UP or
DOWN will change the enable state between “Yes” and “No”. Pressing ENTER will save the state.
When set to “Yes” the trip reset latch function is enabled and the below functions are automatically
assigned to the digital inputs shown below.
NOTE
Assigning the below inputs to the Trip / Reset Latch function DOES
NOT override any previous assignments. I.e. If the “Shutdown on DI1”
function is enabled the UPS will shut down on DI1 regardless of the Trip
/ Reset Latch function.
Table 7: Trip / Reset Latch Operation
DI2
(Trip Input)
DI1
(Reset Input)
State
Relay (Selectable)
(Output)
Low
Low
Healthy
Closed
Low
High
Healthy
Closed
Low
Toggle (Low-High-Low)
Healthy
Closed
High
Low
Tripped
Open
High
High
Tripped
Open
High
Toggle (Low-High-Low)
Tripped
Open
Low
Low
Tripped
Open
Low
High
Tripped
Open
Low
Toggle (Low-High-Low)
Healthy
Closed