12.9 Event Log
A real time clock/calendar is included in the IPM Relay. This combines with the non-volatile memory to
provide a data-logging feature. This log sequentially records the time, date and details of the most recent
event. A chronological list of the previous 50 events is stored.
The event log can be viewed by using the right or left arrow keys to scroll the log.
Event Log 1
Record#01: Power Up
We 26/07 14:57:13.64
We 26/07 14:58:21
A typical display shows:
L2: Displays the event.
L3: Indicates the time that the relay powered up on Wednesday, 26 July.
L4: Indicates the present time.
Log 1 is always the most recent event. Each time a new log is recorded, the 50th log is removed from
the list.
The following events are logged:
Table 8: Events
Event
Description
Power Up
The instant that power is applied to the relay
Pwr Down
Removal of power from the relay
MCR Close
Closure of the Main Contactor Relay
Stopped
Stopping of the outlet by operation of the local stop
button
Ext. Stop
Stopping of the outlet by operation of the external
stop button
MC Opened
Main Contactor has opened but not initiated by the
IPM Relay
MC Fail
Main Contactor Fail Function Trip
CloseFail
Indicates that the MCI Input did not close within 5
seconds of MCR closing
EC Ω Trip
Pilot/Earth continuity loop exceeds 45 Ohms
EC Leak T
Leakage resistance between the pilot and earth is
less than 1500 Ohms
EL Trip
Earth leakage protection tripped
Burp Done
Burp sequence completed
Burp Fail
Burp sequence failed to complete
SC Trip
Trip condition of short circuit protection
OC Trip
Trip condition of overload protection
I bal-Trp
Current balance trip condition
RESET
Records resetting of a protection trip function
Setup Mod
Records that set up data has been modified
Und.I Trp
Under Current Trip caused outlet to stop
uvolt trp
Records that voltage was not present on at least