Message and Type
Comment
RTM Memory Error (see
Note 1)
3
IPM detected errors in set up data received from RTM
Stopped - IPM
3
IPM Stop digital input activated (closed)
RTM CT Ratio Error (see
Note 2)
3
The attached RTM was set up using a different CT
ratio than that of the IPM in use
RTM Version Error
3
The attached RTM does not support 100:1 CT
operation
Remote Stop
3
Shown whenever RTM‟s digital input is open
Configuration Error
2
Present when:
Start is set to Modbus.
In snore mode; the delay or undercurrent trip level is
not set. Also if the remote start is set to „yes‟ or „aux‟
whilst in snore mode.
Stopped
– Ext Stop
3
IPM Stop digital input externally activated (closed).
NOTE
1.
It is normal to see the IPM Memory Error Message when
switching between Diode/RTM Mode or when the RTM is first
connected to the pilot.
2.
If the CT Ratio is changed the current setting must also be reset
(otherwise an Error Message of "RTM CT Ratio Error" will be
displayed).
12.3 Last Trip Status Messages
The IPM Relay has several functions, which can stop/trip the outlet and then self-clear. The IPM Relay
therefore saves the non-
latched trip codes in a register and displays the „Last Trip‟ messages in the
Status Message Page (note that the stop/trip function also appears in the Event Log).
Messages that are displayed at Last T: ---------
Table 4: Last Trip Messages
Message and Type
Comment
EC Leak T
E/C Leakage Trip that provides additional
information for E/C Trip
EC Ω Trip
E/C Ohms Trip that provides additional
information for E/C Trip
MC Opened
Main contactor opened
– opening not initiated
by the IPM Relay