Ampcontrol IPC1 Скачать руководство пользователя страница 19

IPC1 USER MANUAL ISSUE 9  

-15-

 

Ensure  that  the  earth  connections  are  reliably 
installed,  as  this  is  the  basis  of  protection,  for  all 
barriers, including the CCMC. 

(D) Overload & Earth Leakage Toroids 

Current  transformers  are  not  ideal  devices  and  if 
correct  procedures  are  not  followed  during 
installation, nuisance tripping can result. 
 
If,  for  example,  we  consider  a  single  phase  earth 
leakage system where active and neutral pass through 
a toroid, then at all times currents in the two wires are 
equal and opposite so that the net current through the 
toroid  is  zero.    An  ideal  current  transformer  would 
have all the flux from each wire contained in the core 
and  so  would  accurately  add  the  opposing  fluxes  to 
get a net result to zero.  A real current transformer has 
“leakage fluxes”. That is, a very small proportion of 
the total flux from each cable is not contained in the 
core, but  in  the  space outside it  and  as  result  it  may 
link  some  turns  but  not  others,  depending  on  the 
positioning of the cables.   
 
The  effect  of  this  is  that  a  small  output  may  be 
obtained from the CT where none would arise if the 
device were ideal. 
 
The size of the error will vary from CT to CT of the 
same  type  because  of  slight  differences  in  the  core 
and the symmetry of the winding. 
 
Problems  caused  in  this  way  become  worse  as  CT 
sizes  increase,  as  currents  increase  and  a  decrease 
occurs  in  the  symmetry  of  the  cables.  Nuisance 
tripping  tends  to  occur  when  the  total  current  rises, 
such as when a large motor is started. 
This is not normally a problem with the current levels 
found in flameproof enclosure applications.  To help 
avoid  problems  in  other  applications,  select  the 
smallest internal diameter CT, to suit the cable size. 

(E) Toroid Installation Guide Lines 

1.

 

Keep cables as close to the centre of the toroid 
as possible.  Do not tie them to one side of the 
toroid.  Remember to aim at symmetry.

 

2.

 

Do  not  bring  the  cables  back  past  the  toroid 
within one diameter of the CT, trying to cram 
cables  into  a  small  space  reduces  symmetry 
and may lead to problems, which are difficult 
to solve.

 

3.

 

Avoid placing the CT near any device, which 
produces  magnetic  fields  -  whether  it  is  a 
transformer  or  other  cables.    Try  to  maintain 
several CT diameters clearance.

 

4.

 

Many small cables tend to be worse than say 
three large ones.  Try to position the CT in the 
circuit with this in mind. 

12.2 Wiring Installation 

The connections to the IPC Relay consist of a mix of 
intrinsically  safe  circuits  through  to  “high”  voltage 
supplies  and  relay  contact  circuits.  To  ensure  the 
integrity  of  the  intrinsic  safety  is  maintained  and  to 
reduce induction from high voltages, care needs to be 
taken in the layout of the wiring and the installation. 
 
For installations on high voltage systems (>3.3kV) it 
is  advisable  to  install  a  power  supply  filter,  eg 
Schaffner  FN612-1106  (1A,  250VAC  chassis 
mounted  filter)  adjacent  to  the  IPC  Relay. The earth 
should be connected to Pin 7 on the relay as directly 
as possible. 
 
The  IPC  Relay’s  approval  requires  that  the  relay  is 
installed  in  accordance  with  the  Australian  Standard 
for  Intrinsic  Safety  Installation  AS2381.7.  Anyone 
installing  IPC  Relays  should  therefore  have  a  good 
understanding of AS2381.7. 

(A)

 

Intrinsically Safe Circuits: 

Duty 

Pin 

Signal 

Recommended Cable 

Type 

Pilot Core 


Pilot 
Earth 

Single core screened 
Screen  =  0V  (See  note 
1, page 15) 

Serial 
Comms 
Port 



10 
11 
12 

+Vsc 
TXE 
TXD 
RDI 
OV 

Four core screened 
*Screen = OV 

Remote 
Display 

13 
14 
12 

Data 
+Vdm 
OV 

Two core screened 
*Screen = OV 

Note  1: 

That  the  0V  is  internally  connected  to  the 

IPC  Relay’s  earth    (pin  7).  The  screen  therefore 
should NOT be earthed at any other point. 

 
It  is  recommended  that  these  circuits  be  separately 
loomed from all non-IS circuits. 

(B) Low Voltage Signals 

Although these signals are not IS signals themselves, 
they  connect  to  the  low  voltage  side  of  the  IPC 
Relay’s  internal  “infallible”  transformer.  This 
transformer is designed and certified to comply  with 
section 3.2.2 of AS2380.7.  This means that it “is not 
liable to become defective in such a manner as would 
lower  the  intrinsic  safety  of  the  circuit”,  (from 
definitions section of AS2380.7). Care must therefore 
be  taken  to  ensure  these  circuits  cannot  come  into 
contact  with  higher  voltages  (eg  via  insulation 
breakdown, or broken  wires etc). It is recommended 
that these circuits be run in a separate loom from both 
the  IS  circuits  and  the  “high”  voltage  circuits.  To 
ensure  that  interference  is  kept  to  a  minimum,  the 
following cabling is recommended. 
 

Содержание IPC1

Страница 1: ... Australia by Ampcontrol Pty Limited ACN 000 915 542 Phone 02 4903 4800 Fax 02 4903 4888 www ampcontrolgroup com No copies of the information or drawings within this manual shall be made without the prior consent of Ampcontrol USER MANUAL 119051 ISSUE 9 13 02 13 ...

Страница 2: ...stem and or manual without obligation to notify any person or organisation of these changes Before You Begin We would like to take a moment to thank you for purchasing the IPC Integrated Protection Relay To become completely familiar with this advanced protection and control relay system and to ensure correct operation we recommend that you take the time to read this user manual thoroughly IPC Sof...

Страница 3: ...voltage Trip 8 5 3 Voltage Metering 8 6 Fan Control 6 1 Fan Interlocking 9 6 2 Interlocking Sequence 9 7 User Adjustable Settings 7 1 Parameter Groups 9 7 2 Changing Settings 10 8 System Control 8 1 Digital Inputs 11 8 2 Output Relays 11 8 3 Open Collector Outputs 11 8 4 Outlet Control 11 8 5 Operational Sequence 12 9 Event Log 12 10 Time Date 13 11 Remote Data Communications 13 12 Installation Wi...

Страница 4: ...kV Cable Connecting Module 31 IPA A 033 110V Cable Connecting Module 32 IPA S 005 IPA IPB Relay LED Output Module 33 IPA A 031 Relay Output Module General Arrangement 34 IPB A 029 Relay Base Installation Drawing 35 IPC A 023 IPC Baseplate Details Including Permanent Locating Pin and Connection Details 36 17 Approvals NSW MDA Ex ia 10035 ANZEx 08 4071X ...

Страница 5: ...t virtually no external control is required See Typical Connection Diagram IPC E 001 Page 20 Extensive information display and monitoring features are included to facilitate fault finding and system trending This information can be read locally on the Remote Display Module RDM 1K or remotely via a communication link Opto Isolated Outputs are available for connection to optional LED or Relay Module...

Страница 6: ... alarm level 1 5 x selected trip level Last T 1 Shows Last Trip record Need IPC Start 2 Awaiting IPC start digital input Need RTU Start 2 Awaiting RTU start digital input Outlet Paused 2 IPC waits 5 Sec between running or testing and re testing Message and Type Comment Closing MainCont 2 MCR closed waiting for MCI feedback 5 Sec max EFLO Testing 2 In process of EFLO Test 1 second Insulat Testing 2...

Страница 7: ...perational only and that any emergency stops should be wired direct into the pilot circuit PTC terminals are provided for a semiconductor thermistor connection These terminals are protected in a similar manner to the stop and start circuits If the remote stop start and PTC functions are not required each set of terminals must be bridged or the IPC Relay will not energise Four RTD inputs are provid...

Страница 8: ...3kV IPC Cable Connection Modules CCMC are the preferred modules and must be used when the Insulation Test function is required IPA IPB Cable Connecting Modules CCMA are available for the same rated voltages for use with the IPC Relay The use of these modules only allows the normal Intrinsically Safe EFLO Test to be carried out The High Voltage DC Insulation Test is not available with the CCMA Modu...

Страница 9: ...Test The accuracy of the insulation test and expected trip ranges are outlined in the table below The results from insulation test should only be used as a guide to confirm that insulation remains above the preset threshold Insulation tests apart from the generated insulation test via the IPC and CCMC should be still carried out on a regular basis for maintenance purposes Actual Fault Resistance M...

Страница 10: ... which in turn opens the main contactor control circuit The fault can be configured as latching or non latching This allows the user to determine if the fault is manually or automatically reset once the pilot earth loop is healthy The selection is either Pilot Latch On or Pilot Latch Off Level 9 Position 11 To manually reset the relay operate the reset button The EC LED on the Remote Display Modul...

Страница 11: ... the motor being protected Typically the capacity of a cold motor is given at six times its rated current The IPC trip curves can be used to select the time multiplier which best suits the motors overload capacity Thermal Model Thermal modeling is based on a thermal time constant of 30 minutes time multiplier setting of 1 0 times The time multiplier can reduce this value to a minimum thermal time ...

Страница 12: ...0 20 50 and off The phase current balance protection is inhibited until the average current exceeds both 20 of the selected full load current and the selected balance trip level If the trip level is exceeded a timer is triggered If the imbalance remains above the set level for more than two seconds the relay trips The event log records Ibal to differentiate it from a true overcurrent trip The stat...

Страница 13: ...outlets allowing them to run when the fan current is above the selected threshold setting Each relay has the ability to read and drive the FIO link via the Fan Input Read FIR processor input and the Fan Interlock Drive FID processor output The status of the input output can be viewed on the Remote Display Module Relay and Digital Input Status Section Level 6 Position 4 The outlet control in each I...

Страница 14: ...trip threshold as a of line volts SC Relay Selects which output relay MCR or CBR is tripped in event of a short circuit trip EC Time Sets the trip time for the earth continuity protection Relay 3 Selects off FID or FIR operation of the relay The second group of settings consists of parameters that are related to the load connected to the protected outlet These settings are stored retrieved to from...

Страница 15: ... the stored values the old value and the new value are stored in the event log A separate log immediately proceeds this recording the time and date that the change was made Note 1 While in the diode mode the IPC Relay can be preset with operating values in the Group 2 memory prior to switching to the RTU mode When in this mode the relay uses the Remote Termination Unit settings If the Remote Termi...

Страница 16: ...ollector output on the relay is switched on to provide remote monitoring if required A time delay of 5 seconds is allowed for the Main Contactor Interlock MCI to close If it does not close within this time then the run mode is exited If a stop input is closed while the relay is in run mode the run is cleared and the MCR relay de energises The event log reads Stopped If a stop input is closed durin...

Страница 17: ...eset to zero Mem ERROR Records that the relay s non volatile parameter memory has been corrupted P reset Internal microprocessor reset Tmem Loss The thermal memory data has been corrupted RTU mem E Records that the remote termination unit s non volatile memory has been corrupted or remote termination unit has gone off line while the outlet is running Outlet On Records RTU machine code and number w...

Страница 18: ...a powder coated sheet steel enclosure designed to be mounted into existing enclosures ie flameproof equipment or other enclosures of adequate IP rating The relay is designed to operate when mounted either laid down flat or in a vertical position Vent holes are provided at both the top and bottom of the relay to assist in the cooling of the electronics inside the relay These vents should not be blo...

Страница 19: ...hether it is a transformer or other cables Try to maintain several CT diameters clearance 4 Many small cables tend to be worse than say three large ones Try to position the CT in the circuit with this in mind 12 2 Wiring Installation The connections to the IPC Relay consist of a mix of intrinsically safe circuits through to high voltage supplies and relay contact circuits To ensure the integrity o...

Страница 20: ...tage Circuits The high voltage circuits of the IPC Relay are the 110VAC supply pins 30 31 and the relay contacts Apart from keeping these separate from the other wiring to the relay there are no special requirements In accordance with Australian Standards the relay contacts of the IPC Relay must not be used to switch more than 190VAC 5A or 100VA the intrinsic safety will be compromised if any of t...

Страница 21: ... Range 7 5 to 464 Amps 60 to 116 Amps in 4 Amp increments times current multiplier Current Multiplier 1 8 1 4 1 2 1 2 4 times Time Multiplier 0 005 0 01 0 015 0 02 0 03 0 04 0 05 0 075 0 1 0 15 0 2 0 3 0 4 0 5 0 6 0 7 0 8 1 0 times Cooling Multiplier 0 2 0 3 0 4 0 5 0 8 1 0 2 0 5 0 10 20 50 times Current Balance Trip Settings 5 10 20 50 and off Short Circuit Protection Trip Setting 3 0 to 10 0 tim...

Страница 22: ...mine the Group 1 and 2 Settings level 8 and 9 to check the stored parameters in the non volatile memory Machine type and number are irrelevant and should be ignored One or several settings will show Re program lost settings into the memory 7 8 Status Message IPC Memory Error When in RTU pilot mode Corruption in the Group 1 Settings in the IPC Relay Examine the Group 1 Settings level 8 to check the...

Страница 23: ...ion 2 Check that main contactor is closing If not check circuit or replace main contactor Check auxiliary contacts and wiring 10 RDM displays Tripped No Volts message Relay not receiving lost voltage feedback on one or all three outlet phases when contactor closed Check system voltage display level 4 position 1 as contactor closes Compare this with the under voltage threshold 6 Check continuity fr...

Страница 24: ......

Страница 25: ...AMPCONTROL PTY LTD 21 ...

Страница 26: ...AMPCONTROL PTY LTD 22 ...

Страница 27: ... 23 ...

Страница 28: ...Integrated Protection I P C Relay type B DCB Integrated Protection I P C Relay type B Integrated Protection I P C Relay type B Integrated Protection I P C Relay type B 24 ...

Страница 29: ...UP RESISTANCE 45 Ohms DROP OUT RESISTANCE RTU or Local Mode 45 Ohm Remote Diode Mode 145 Ohm TERMINATION UNIT Ampcontrol RTU 1 RTU 2 or Diode CABLE C 0 3uF L 10mH L R 600uH Ohm EARTH FAULT LOCKOUT CCMA 415 or CCMC 415 WARNING Main Contactor Fail AUSTRALIAN MADE Designed Manufactured in Australia by CCMA 1000 or CCMC 1k CCMA 3 3k or CCMC 3 3k 415Vac 1000Vac 3 3kVac 4 15 k Ohms 10 k Ohms 33k Ohms Sy...

Страница 30: ...It is subject to their recall and must not be reproduced in part or in whole or its contents divulged to third parties without prior written approval from Ampcontrol Pty Ltd SHEET REV A3 1 CRN 0 CRN APPROVED CHECKED DRAWN SCALE NAME DATE D P 16 07 97 1 1 RYU_2 GENERAL ARRANGEMENT IPB REMOTE TERMINATION UNIT IPB A 021 1 7066 3963 22 09 08 04 04 97 G F E D C B A G F E D C B A AMPCONTROL CSM PTY LTD ...

Страница 31: ...N AS1100 ALL DIMENSIONS IN MILLIMETRES UNLESS STATED OTHERWISE 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 This drawing remains the property of Ampcontrol Pty Ltd It is subject to their recall and must not be reproduced in part or in whole or its contents divulged to third parties without prior written approval from Ampcontrol Pty Ltd SHEET REV A3 1 CRN 0 CRN APPROVED CHECKED DRAWN SCALE NAME DATE D...

Страница 32: ... 0Vac E 110V OCO com OCO0 OCO1 OCO2 OCO3 OCO4 OCO5 OCO6 OCO7 Vsc TXD RDI Data 0V Vdm MCR RL3 CBR FIO Ampcontrol IPC Base STOP RL4 1 2 3 4 5 6 A B 7 8 9 10 11 12 Insulation Test 1 2 3 4 5 6 A B 7 8 9 10 11 12 1 2 3 4 5 6 A B 7 8 9 10 11 12 1 2 3 4 5 6 A B 7 8 9 10 11 12 242 0 mm 256 0 mm 152 0 mm 120 0 mm AMPCONTROL PTY LTD 28 Temporary Locating Guide Part No E09638 To Ensure Correct Orientation of...

Страница 33: ...120 0 mm 140 0 mm 8 0 mm RL4 110Vcom Vcma Vcmb Vcmc Earth CCMC 415 Va Vb Vc AMPCONTROL PTY LTD 29 ...

Страница 34: ...120 0 mm 140 0 mm 8 0 mm RL4 110Vcom Vcma Vcmb Vcmc Earth CCMC 1 0k Va Vb Vc 48 0 mm 70 0 mm AMPCONTROL PTY LTD 30 ...

Страница 35: ...66 mm 66 mm 120 mm RL4 110Vcom VcmA VcmB VcmC Earth Va Vb Vc 70 mm 100 mm 240 mm 100 mm 230 mm AMPCONTROL PTY LTD CCMC 3 3k E07044 31 ...

Страница 36: ... 32 AMPCONTROL CSM PTY LTD ...

Страница 37: ... and must not be reproduced in part or in whole or its contents divulged to third parties without prior written approval from Ampcontrol Pty Ltd SHEET REV A3 0 CRN APPROVED CHECKED DRAWN SCALE NAME DATE ABN 35 000 770 141 7 BILLBROOKE CLOSE CAMERON PARK N S W 2285 AUSTRALIA P 61 2 4903 4800 electronics ampcontrol com au D P 06 01 92 Nil IPA RELAY LED OUTPUT MODULE DETAILS IPA S 005 0 N A G F E D C...

Страница 38: ... and must not be reproduced in part or in whole or its contents divulged to third parties without prior written approval from Ampcontrol Pty Ltd SHEET REV A3 0 CRN APPROVED CHECKED DRAWN SCALE NAME DATE ABN 35 000 770 141 7 BILLBROOKE CLOSE CAMERON PARK N S W 2285 AUSTRALIA P 61 2 4903 4800 electronics ampcontrol com au G R 20 5 94 1 1 IPA RELAY OUTPUT UNIT PCB CARD HOLDER GENERAL ARRANGEMENT IPA ...

Страница 39: ...it must not be opened in a Hazardous Zone as it contains energy storage devices Dangerous conditions may result if this warning is ignored Ensure all settings are appropriate for the instalation PRIOR to putting into Service Caution Do Not Overtighten Flag Tripped Flag Reset Designed Manufactured in Australia VcmA VcmB VcmC Pilot Earth Ia2 Ia1 EL1 EL2 Ic1 Ic2 Lock Reset Start MCI 14 13 12 11 10 9 ...

Страница 40: ...6 45 44 43 0Vac E 110V OCO com OCO0 OCO1 OCO2 OCO3 OCO4 OCO5 OCO6 OCO7 Vsc TXD RDI Data 0V Vdm MCR RL3 CBR FIO Ampcontrol IPC Base STOP RL4 1 2 3 4 5 6 A B 7 8 9 10 11 12 Insulation Test 1 2 3 4 5 6 A B 7 8 9 10 11 12 1 2 3 4 5 6 A B 7 8 9 10 11 12 1 2 3 4 5 6 A B 7 8 9 10 11 12 242 0 mm 256 0 mm 152 0 mm 120 0 mm AMPCONTROL PTY LTD 36 Fixed Locating Guide To Ensure Correct Orientation of Relay IN...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ......

Страница 53: ......

Отзывы: