FireFinder
™
Installation Commissioning & Operation
Page 80
15.8.5
Manual Control Point ( MCP )
Press
q
MCP:
The operator will be prompted to enter the NODE Number, that is the Node or panel on which the
MCP is mounted.
15.8.6 Sub
Address
Press
r
Sub Address lets the operator EDIT or DELETE the address of an IO device on a Loop.
☞
Note:
an input is the only function that can bring up an alarm
.
Select the LOOP, then ENTER , SENSOR, then ENTER then the SUBADDRESS ( eg 1, 2 or 3 for
3IO device ), or press
m
to EDIT or press
n
to DELETE.
Editing
If editing, the screen will display the Loop number, Sensor number and sub address followed by
DESC < TYPE < INPUT > and advise the Alpha keys are active. Once edited and pressing
ENTER the message UPDATE TO MEMORY message will be displayed.
ENTER
should not be pressed
if the CONFIGURATION is to be edited, instead press
to go
to the next screen where the output is configured to be latching (general alarm requiring a Reset to
be returned to normal ), NON-LATCHING ( hence self resetting ) or FAULT which clears when the
fault is cleared. )
15.8.7 Watchdog
s
This Function provides a counter to record any re-initialisation of the processor. If due to a
software failure the panel is automatically reset then the counter will increment by 1 The maximum
count is 99 after which the counter resets to 00. Pressing
m
will reset the counter. When the panel
is commissioned this counter
MUST
be reset to 0 as must be the
Events Logs
.
15.9 Self
Learn
Self Learn is enabled / disabled in the EEPROM programming. If enabled
FireFinder
™
has the ability to
detect extra or missing modules or devices, (that is devices or modules that have been added or removed)
or there has been a change of the type of module or device.
☞
Note:
If a change does occur the FACP will take 30seconds to register the event on the LCD and
illuminate the FAULT LED
.
15.9.1
Extra Devices Detected
The
FireFinder
™
LCD will indicate extra devices have been detected by displaying the screen below
and the FAULT LED will be illuminated.
FIREFINDER 4/7/2005 08:05:45
EXTRA DEVICES DETECTED
GOTO PROGRAMMING MENU TO RESOLVE
SYSTEM IS NOT NORMAL
Figure 106: Resolving Extra Modules And Devices