FireFinder
™
Installation Commissioning & Operation
Page 77
15.6 Function Manual I/O Control
Press
r
to display the Manual I/O Control menu
MANUAL I/O CONTROL
0: INPUT 1: OUTPUT
2: REMOVE MANUAL CONTROL
SELECT NO.
Figure 99: The Manual I/O Control Menu
Manual I/O control allows the technician to turn ON or Off inputs and outputs off a device to facilitate
testing or isolation of plant during maintenance. Removal of manual control returns control to the panel.
Press
m
Input Selected:
Press
m
IN A PANEL:
Enter the I/O Controller number then the input number . This will
display the description for the input and its current state, you can then turn the input
ON or OFF or remove manual control.
n
ON A LOOP:
Enter the loop number , the sensor number and the input number .
This will display the description for the input and its current state, you can then turn
the input ON or OFF or remove manual control.
o
Remove All Manual Input Control:
Will remove all manual input control.
n
Output Selected:
Same sequences as above for inputs but
substitute outputs for inputs.
o
Remove All Manual Control Selected:
Globally removes all manual control.
15.7 Function Access ( Level II ) / Passwords ( Level III )
FUNCTIONS
PASSWORD
select PASSWORD then ENTER key
PASSWORD MENU
0: ADD PASSWORD 1: DELETE PASSWORD
2: DELETE ALL PASSWORDS 3: SENSOR MODE
SELECT NO.
Figure 100:
The Level II Password Entry & Level III Password Menu Screens
Press
s
while in the Main Functions menu and enter the Level III Password if in Access Level II or, if in Access
Level III to display the Password Menu.
m
Add
Password:
Enter the new password, then press
ENTER
. The password is always a
4 digit number.
n
Delete
Password:
Enter the password that you want to delete, then press
ENTER
.
o
Delete
All
Passwords:
This asks you to confirm that you want to delete all the passwords.
Press
ENTER
then
ENTER
again.
p
Zone / Sensor Mode:
This sets the mode in which Alarms, Faults, Prealarms and Isolates
status information will be displayed. “Zone” is the default setting.