Installation Commissioning & Operation
Page 57
Local Control Station Layout
The Local Control Station is supplied with its own mounting panel. The Comms line is RS485 between the
Local Control Station and the Main Control Board.
The Interlock is a monitored input with 10K
Ω
EOL used to determine if air conditioning dampers and doors
are closed. Typically the agent is not discharged until all dampers / doors are closed but can be defaulted
to the “ON” condition by terminating the input with a 2K2
Ω
as shown below.
1
2
3
4
ON
1
2 3
4
ON
1
2 3
4
ON
2
3
4
+27VDC OUT
TO NEXT LCS
+27VDC IN FROM
TERMINATION BRD.
10K
EOL
+
ON
Address
Switch
Set to 1
1
2 3 4
Agent Termination Board
within the FACP
Local Control Station
ONLY USED ON THE LAST
LCS ON THE COMMS BUS
10K
EOL
2K2
INTER
LOCK
INSERT A 2K2 ACROSS
THE 10K EOL TO
DEFAULT TO "ON"
TB4
T1
C N1
LK2
TB2
TB1
S W2
4
3
2
1
LK1
CN5
+
AGENT
MANUAL HOLD/
MANUAL
-
+
RS 485 OUT
RS 485 IN
-
+
RELEASE
0 V
+24V
C O M
LINK
TERMINATOR
C O M
0 V
+24V
BRD25ARB5-
INTER-
LOCK
-
JTAG
INHIBIT
SWITCH MON.
DISABLE
INHIBIT
EOL
RS 485
COMMS
BUS
SIG
SIG
SC
R
N
27
VD
C
0V
DC
+
+
-
TB1
Figure 66: PCB Layout & Cabling Detail
10.6 Agent Release Termination Board
Figure 67: Agent Termination Board PCB Layout
LK1
Q2
SW1
U5
U9
U7
U1
X1
RL6
RL4
RL1
RL2
RL5
RL3
CN5
U3
U4
U2
U10
RL7
+ LOCK-
+ L.PSW-
RELEASE
C
NC
NO
///
+L
COMM
NC
NO
-L
C
NC
NO
///
-
+
SIG+
SIG-
LCS CABLE
+ PSW -
Monitored
INPUTS
N/0
STAGE2
GAS
FIRED
+
-
N/0 COM
N/0 COM
+
SYST.
INOP.
SCRN
+24VDC
+ -
C
NC
NO
///
C
NC
NO
///
-L
NO
NC
COMM
+L
-L
NO
NC
COMM
+L
03
/0
9
/02
0VDC
+ -
STAGE1
-
COM
30
2-
787
0
TB7
TB6
TB5
TB4
TB3
TB2
TB1
C
N
2
C
N
1
Address Setting
CN3 CN4
27V In
27V to
Next Board
RS485 Control
In From CN2 of
Previous Board
or CN21 of the
Main Control
Board
RS485 Control
Out to Next
Board or Link 1
EOL is Applied
MAIN
RESV
+ - Outputs are Monitored
Contact
Rating
1A & 24V
Contact
Rating
1A & 24V
Contact
Rating
1A & 24V
Contact
Rating
1A & 24V
1 2 3 4
O N
EOL
Termination