The controller compares the temperatures at the coll-
ector sensors S1 and S5 to the store temperature at
sensor S2. If one of the measured temperature diffe-
rences is higher than the adjusted switch-on temperature
differences, the corresponding pump (R1, R2) or both
pumps will be activated and the store will be loaded.
Heat transfer control to an existent store (R3) can be
carried out with another temperature differential function
(S3-heat source/S4-heat sink).
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
18
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT S
10 K
Set temperature difference
RIS
2 K
Rise
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL 1 >
Collector 1
CEM1
115 °C
Collector emergency temperature 1
OCCO1**
OFF
Option collector cooling 1
CMAX1
95 °C
Maximum collector temperature 1
OCMI1
OFF
Option collector minimum limitation 1
Sensor/Ter-
minal
Designation
Description
S1
TCOL1
Temperature collector 1
S2
TST1B
Temperature store 1 base
S3
TSTT
Temperature store 1 top
S4
TST2B
Temperature store 2 base
S5
TCOL2
Temperature collector 2
VFS
Optional sensor for measurement
purposes or options
RPS
V40
Relay
Description
R1
Solar pump collector 1
R2
Solar pump collector 2
R3
Heat exchange pump
R4
optional:
Thermal disinfection
Parallel relay
Heat dump
System 18
Solar system with east-/west collectors and heat exchange control
R3
R2
R1
S5
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in