Level 5
System 2
Solar system with 2 stores and heat exchange
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
Heat exchange between S3 and S4 is possible.
Relay
Description
R1
Solar pump
R2
Heat exchange pump
R3
optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump
R4
Sensor/Ter-
minal
Designation Description
S1
TCOL
Temperature collector
S2
TST1B
Temperature store 1 base
S3
TST1T
Temperature store 1 top
S4
TST2B
Temperature store 2 top
S5
Optional sensor for measurement
purposes or options
VFS
RPS
V40
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
2
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT S
10 K
Set temperature difference
RIS
2 K
Rise
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL >
Collector
CEM
115 °C
Collector emergency temperature
OCCO**
OFF
Option collector cooling
CMAX
95 °C
Maximum collector temperature
OCMI
OFF
Option collector minimum limitation
R2
R1
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PW
M
2
N
R4
V4
0
L'
VFS
RPS
out
in