AMK Solac 11252 DeltaSol_BX.monen.ind
d
23
|
Level 5
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
With another temperature differential function (S4/S3),
afterheating of the store can be carried out with a solid
fuel boiler (R3).
Sensor/Ter-
minal
Designation
Description
S1
TCOL
Temperature collector
S2
TSTB
Temperature store base
S3
TSTT
Temperature store top
S4
TSFB
Temperature solid fuel boiler
S5
Optional sensor for measurement
purposes or options
VFS
RPS
V40
Relay
Description
R1
Solar pump
R3
Loading pump solid fuel boiler
R2
optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump
R4
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
8
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT S
10 K
Set temperature difference
RIS
2 K
Rise
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL >
Collector
CEM
115 °C
Collector emergency temperature
OCCO**
OFF
Option collector cooling
CMAX
95 °C
Maximum collector temperature
System 8
Solar system with 1 store and afterheating with solid fuel boiler
R3
R1
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PW
M
2
N
R4
V40
L'
VFS
RPS
out
in