amiad EBS-10000 Скачать руководство пользователя страница 18

 

EBS 10000 IL                                                                           910101-000109 / 09.17 

Page 18 of 24 

PARTS SCHEDULE 

Refer to drawing on pages 19 

 21 

 

No. 

CAT. No. 

DESCRIPTION 

Qty. 

710105-002603 

10"EBS10K HOUS IL ASA150 EPXY555 ICEA300 

760102-000068 

HEX NUT M20 ZINC PLATED C/ST DIN934 

16 

760103-000070 

FLAT WASHER M20 DIN125 ZINC PLATED C/ST 

32 

770102-000188 

O-RING SEAL P2-471 (EBS-10000 LID)NBR 

710105-001639 

SCRN SUPP EBS-10K/MEGA CI AMRLK 400 

770102-000126 

O-RING SEAL (P2-237) NAT 

710103-002924 

LOWER BEARING EBS-40K/EBS-15K 

770101-000059 

O-RING SEAL71X5UP.BEARING DISC EBS NBR S 

770104-000076 

SHAPED SEAL HYD.AM-04NR EBS10000 SCR.NBR 

10 

700101-001033 

WEAVEW.ST316 10000SQ.CM S300MIC F/EBS10K 

11 

700190-002639 

SUCT SCAN ASSY WITH INTERNAL 

12 

710103-002547 

SUCTION SCANNER SHAFT EBS 

13 

760105-000043 

PIN 10X53 S/ST316 

14 

710103-002948 

PLUG M12 FOR MEGA 19BAR 

15 

700190-002736 

SCANNER ASSY OUTLET FILTER EBS-40000 

16 

710103-002827 

PLUG POM FOR INTERN FILTER SCAN,EBS-15K 

17 

710103-002534 

SUCTION SCANNER NOZZLE EBS 

18 

770101-000059 

O-RING SEAL71X5UP.BEARING DISC EBS NBR S 

19 

710103-002611 

UPPER BEARING EBS 

20 

770102-000077 

O-RING SEAL P2-041EXTERN.UP.BEAR.G97NBR 

21 

710105-001502 

LID EBS-10K ASA150/BS EPOXY555 ICEA-3002 

22 

760101-000358 

HEX BOLT PARTIAL TH M20X100 Z.PLT C/ST 

16 

23 

770102-000168 

O-RIN.P2-433DRIV.UN.AD.EBS H-SAF NBR N/F 

24 

710105-001473 

DR SHAFT HOUS EBS-10K EPOXY PKPK-3002 

25 

760101-000328 

HEX BOLT PARTIAL THR M16X60 Z.PLT C/ST 

26 

760103-000069 

FLAT WASHER M16 DIN125 ZINC PLATED C/ST 

16 

27 

760102-000067 

HEX NUT M16 ZINC PLATED C/ST DIN934 

28 

710105-001474 

DR SHAFT HOUS COVER EBS EPOXY PKPK-3002 

29 

720202-000018 

GEAR RMI70 FL 1/70 71 B5 

30 

760101-000314 

HEX BOLT FULL THRD M10X40 Z.PLT C/ST 

31 

760103-000067 

FLAT WASHER M10 DIN125 ZINC PLATED C/ST 

32 

760103-000086 

SPRING WASHER M10 DIN127 ZINC PL. C/ST 

33 

760102-000064 

HEX NUT M10 ZINC PLATED C/ST DIN934 

34 

710105-001582 

DR SHAFT COVER EBS GEAR EPOXY PKPK-3002 

35 

760101-000524 

SOCKET HEAD CAP SCREW M8X30 S/ST316 

36 

770103-000046 

FLANGE GASKET 3" 124X92 NBR 

37 

730103-000517 

3" BERMAD (400) HYD. VALVE ASA150 RED 

38 

760101-000329 

HEX BOLT PARTIAL THR M16X65 Z.PLT C/ST 

39 

760103-000069 

FLAT WASHER M16 DIN125 ZINC PLATED C/ST 

40 

760102-000067 

HEX NUT M16 ZINC PLATED C/ST DIN934 

41 

730104-000220 

BALL VALVE 3/4" M/F (BRASS/NI) 

42 

780101-000789 

L-CONNECTOR 3/4" F/M GALVANIZED 

43 

010000-000042 

3/4" FILTER BSPT AC BLACK SCREEN 200 MIC 

44 

770102-000082 

O-RING SEAL P2-112 NBR"S" 

45 

710103-002569 

RACCORD NIPPLE 1/4" FOR 3/4" FILTER 

46 

710103-002570 

RACCORD NUT 3/4" FOR 3/4" FILTER 

47 

720501-000202 

L-CONNECTOR 5/16"X1/4" 69F BRASS 

48 

710103-000591 

PRESS CH POINT CONNECTOR 1/4"X1/4" BRASS 

49 

720103-000182 

SOLENOID VALVE 24VAC NO ASCO RED HAT 

50 

720501-000206 

CONNECTOR 5/16"X1/4" 68F BRASS 

51 

720502-000036 

CONTROL TUBE 5/16" NYLON AIR BREAK 

2.2M 

 
 

Содержание EBS-10000

Страница 1: ...01 000109 09 17 Page 1 of 24 AMIAD WATER SYSTEMS EBS 10 000 IN LINE FILTER Serial number Order number Catalogue number Filtration degree Tested by Installation Operation and Maintenance Instructions 910101 000109 09 17 ...

Страница 2: ... content The confidential nature of and or privilege in the file enclosed is not waived or lost as a result of a mistake or error in this file If you received this file in error please notify Amiad immediately at info amiad com This document does not replace any certified drawing procedure or information provided by Amiad in reference to a specific customer site or project Amiad assumes that all u...

Страница 3: ... 8 Description and filter operation 9 Installation 10 Commissioning Start up and First Operation 11 Maintenance 12 Troubleshooting 14 Disassembling and reassembling 15 Parts schedule 18 Parts drawing Section 1 20 Parts drawing Section 2 21 Parts drawing Section 3 22 Limited Warranty 23 With any inquiry please quote Filter Serial Number located on the filter housing ...

Страница 4: ... Flush data Exhaust valve 80mm 3 Flushing cycle time 30 40 seconds 30 40 seconds Wasted water per cycle 500liter 132USgal at 2bar 30psi Minimum flow for flushing 50m h 220USgpm at 2bar 30psi Control and electricity Electric motor 1 2 HP 50 60 Hz 18 22 Gear output R P M Rated operation voltage 3 phase 220 380 440 V 50 60 Hz Single phase 110 220 V 50 60 Hz Control voltage 24V AC Current consumption ...

Страница 5: ...ting at the area of the filter to enable good visibility and safe maintenance The user should arrange suitable platforms ladders and safety barriers to enable easy and safe access to the filter without climbing on pipes and other equipment The user should verify that any platform barrier ladder or other such equipment is built installed and used in accordance with the relevant local authorized sta...

Страница 6: ... note that the maximum working pressure indicated at the filter s specifications table includes the pressure caused by fluid hammer and pressure surge effects Civil Engineering Make sure that the filter installation is done by Amiad qualified technicians Make sure that any civil engineering work at the installation site such as construction lifting welding etc is done by qualified workers technici...

Страница 7: ...ze slippage electrification or damage to the equipment caused by moisture While using lifting equipment make sure that the filter or the lifted part is chained securely and in a safe manner Do not leave lifted equipment if there is no necessity Avoid working below lifted equipment Wear a safety helmet goggles gloves and any other personal safety equipment required by the local standards and regula...

Страница 8: ...EBS 10000 IL 910101 000109 09 17 Page 8 of 24 DIMENSIONAL DRAWING ...

Страница 9: ...e timer in the control board to CONT position 4 Malfunction mode During malfunction mode the self cleaning operation is stopped the malfunction light on the control board is turned on and an external output is activated with 24V AC The filtration system may enter a malfunction mode in the following cases 1st When there is a continuous signal from the pressure differential switch for duration of mo...

Страница 10: ...remove large objects that may damage the filter s internal mechanism 7 Install a drainage pipe to the exhaust valve Minimum 3 diameter for a maximum pipe length of 20 meters 60 feet for longer drainage 4 pipe diameter must be used for a maximum length of 40 meters 120 feet Please note that no restriction is allowed on the drainage pipe For special applications please consult the manufacturer 8 If ...

Страница 11: ...ntrol 24V circuit breakers and the motor protector to ON The motor will start operating The suction scanner shaft should turn clockwise and move downward to the filter housing until it reaches the lower limit switch If the motor rotates in the opposite direction disconnect the electricity immediately and change the direction of the motor rotation by changing between two phases The motor must stop ...

Страница 12: ...e filter carefully and safely to its water air and power supply 7 Perform a General Inspection of the Filter Operation as described above Changing the sealing flange internal O ring 1 Close the inlet valve to the filter and release any residual pressure 2 Disconnect and lock the filter s power supply 3 Disconnect and lock the filter s compressed air supply and release any residual pressure 4 Verif...

Страница 13: ...ter housing or accessories h Unusual vibrations i Non smooth operation of the filter valves air release valves and check valves 2 Close the inlet and the outlet valves of the filter Drain the filter housing and release any residual pressure 3 Disconnect and lock the filter s power supply 4 Disconnect and lock the filter s compressed air supply and release any residual pressure 5 Disassemble the fi...

Страница 14: ...if found faulty The motor protector was activated The fault indication lamp is blinking in red This fault means that the motor was operated under too high load Note All the following checks and actions should be done by a qualified electrician only A Check the motor power consumption when not loaded B Check the limit switches for correct operation and verify that each one of them stop the motor at...

Страница 15: ...58 then pull out the connecting pin If the connecting pin is not facing one of the shaft housing windows turn the drive shaft 56 a little Use 17mm or 11 16 spanners 7 Turn the drive shaft 56 counter clockwise so that it will be separated from the suction scanner shaft 12 8 Unscrew bolts 61 and remove the limit switches sling without disconnecting and changing the limit switches position 9 Unscrew ...

Страница 16: ...uld be lifted only with Amiad s standard Extractor and a standard lifting device operated by an authorized operator 1 Clean and dry the rubber pads on the Extractor 2 Fold the Extractor upwards Figure 1 Figure 1 3 Insert the Extractor into the screen about a quarter from top Make sure that the extractor cushions do not touch the stitch found along the screen interior 4 Pull the extractor up so tha...

Страница 17: ...with two bolts 22 in opposite positions 6 Screw the rest of the housing bolts 22 Tightening opposite positioned bolts will achieve proper sealing 7 Locate the O ring 23 in its groove under the shaft housing 24 Place the bolts 25 but do not yet tighten them firmly 8 Turn the drive shaft 56 clockwise until it reaches the suction scanner shaft Insert the connecting pin 58 into the hole in the drive s...

Страница 18: ... NBR N F 1 24 710105 001473 DR SHAFT HOUS EBS 10K EPOXY PKPK 3002 1 25 760101 000328 HEX BOLT PARTIAL THR M16X60 Z PLT C ST 8 26 760103 000069 FLAT WASHER M16 DIN125 ZINC PLATED C ST 16 27 760102 000067 HEX NUT M16 ZINC PLATED C ST DIN934 8 28 710105 001474 DR SHAFT HOUS COVER EBS EPOXY PKPK 3002 1 29 720202 000018 GEAR RMI70 FL 1 70 71 B5 1 30 760101 000314 HEX BOLT FULL THRD M10X40 Z PLT C ST 4 ...

Страница 19: ...X16 S ST304 DIN916 2 74 760101 000527 SOCKET SET SCREW M10X50 S ST316 DIN916 2 75 760103 000097 FLAT WASHER M10 DIN125 S ST316 2 76 760102 000087 HEX NUT M10 S ST316 DIN934 2 77 700190 002336 MANOMETER VALVE 1 4 W DRAIN 1 78 720501 000214 T CONNECTOR1 4 FX1 4 FX1 4 M NICKEL PLA 2 79 720501 000202 L CONNECTOR 5 16 X1 4 69F BRASS 2 80 730104 000202 VALVE 3 WAY 1 4 SAGIV SY3 1Y3NO4OA4 1 81 720501 000...

Страница 20: ...EBS 10000 IL 910101 000109 09 17 Page 20 of 24 PARTS DRAWING Section 1 ...

Страница 21: ...EBS 10000 IL 910101 000109 09 17 Page 21 of 24 PARTS DRAWING Section 2 ...

Страница 22: ...EBS 10000 IL 910101 000109 09 17 Page 22 of 24 PARTS DRAWING Section 3 ...

Страница 23: ... This warranty is valid on the condition that the Products are installed according to Amiad s instructions as expressed in Amiad s instruction manuals and according to the technical limitations as stipulated in Amiad s literature or as stated by a representative of Amiad 7 This warranty will not apply to damaged or defective Products resulting from or related to i Fire flood power surges or failur...

Страница 24: ...233500 Israel Tel 972 4690 9500 Fax 972 48141159 Email info amiad com Obelis s a Bd Général Wahis 53 1030 Brussels Belgium Tel 32 2732 5954 Fax 32 27326003 Email mail obelis net EC Declaration http amiad com pdf certificates MACHINERY_SAFETY pdf ...