Amiad Water Systems - ADI-X IOM 910101-001180 / 06.2021
69
5.5
ADI-X Controller Counters Reset
ADI-X Controller has five flushing cycles counters:
1.
Total flushing cycles
–overall number of cycles performed by the controller during
operation. This number cannot be reset.
2.
DP cycles
– number of flushing cycles started due to a DP signal.
3.
Flushing Interval cycles
– number of flush cycles started due to the time intervals settings.
4.
Manual cycles
– number of flush cycles initiated manually by the user.
5.
Preset cycles
– number of flush cycles started due to the preset start times.
Counters 2-5 can be reset via
ADI-X Desktop
application,
ADI-X Mobile
application, and
ADI-BLE
Mobile
application.
To reset the counters using
ADI-X Desktop
application:
1.
Sign in to
ADI-X Desktop
application.
2.
Go to "Sites" tab in left menu and select the required site.
3.
Go to "Overview" tab and click "Reset" in the Flushing Cycles field. The counters will reset.
Figure 60: ADI-X Desktop application. Sites screen, Overview tab