© 2021 AMETEK Power Quality Solutions | Technical Support 800-645-9721 | surgex.com
31
User Manual
9. Specifications
Parameter
Specification
AC Load Rating
Maximum Full Load
North America
12 Amps at 120 Volts
Rest of World
10 Amps at 240 Volts
DC Load Rating
Maximum Full Load
DC Output 1
Rating
DC Output 2
Rating
Combined DC1 +
DC2 Rating
5V Output Rating
SX-DC-8-12-X
5A @ 12V
5A @ 12V
10A @ 12V
3A @ 5V
SX-DC-8-24-X
2.5A @ 24V
2.5A @ 24V
5A @ 24V
3A @ 5V
SX-DC-8-1224-X
2.5A @ 24V
5A @ 12V
NA
3A @ 5V
Power Requirement (no load)
15 Watts
DC Efficiency
90% Typical
Audible Noise at 1m
35 dBA Typical
Heat Generation
185 BTU/h Max
EMI/RFI Filter
Normal mode (50
Ω
load)
> 30 dB 80 kHz
–
50 MHz
Common Mode (50
Ω
load)
> 20 dB 160 kHz
–
27.5 MHz
> 30 dB 310 kHz
–
17.6 MHz
Under-Voltage Auto Shutdown
Adjustable from 0V to 300V, or disabled.
Over-Voltage Auto Shutdown
Adjustable from 125V to 300V, or disabled.
Over-Current Auto Shutdown
Adjustable from 0.1A to 20A, or disabled.
Measurement Accuracy
Voltage
± 2% Typical Product Accuracy
Current
± 2% Typical Product Accuracy
Power
± 2% Typical Product Accuracy
Energy
± 2% Typical Product Accuracy
Timestamp Accuracy
± 1% Typical Product Accuracy
Network Port
10/100 Ethernet connection on Female RJ-45, Auto Negotiating with
10/100 network connections with Link and Activity LEDs
USB RNDIS Device on micro AB
Dimensions
1.75"D x 10"L x 8.25"H
Weight
SX-DC-8-12-X, SX-DC-8-24
-X
5 lb.
SX-DC-8-1224
-X
5.5 lb.
Temperature Range:
100% Load
SX-DC-8-12-X
5C to 39C
SX-DC-8-24-X
5C to 47C
SX-DC-8-1224-X
5C to 42C
Humidity Range
0% to 95% R.H. Non-condensing
Agency Listings
UL/CUL/CB 62368