51. EXTRA RUN TIME The programmed run time
after normal charge complete.
52. PROG. BID If a connected battery is
CELLS equipped with a Battery I.D.
module, the battery cells size
(6,9,12,18,24,36) may be re-
programmed into the BID.
The control must be in
“Manual Stop” status.
53. PROG. BID NO. If a connected battery is
equipped with a Battery I.D.
module, the I.D. number
(000000-999999) may be re-
programmed into the BID.
The control must be in
“Manual Stop” status.
54. PROG. BID AH If a connected battery is
equipped with a Battery I.D.
module, the battery amp-hour
size (0000-9999) may be re-
programmed into the BID.
The control must be in
“Manual Stop” status.
55. PROG. BATT. If a connected battery is
TYPE* equipped with a Battery I.D.
module, the battery type
may be programmed into
the BID. The control must be
in “Manual Stop” status.
00 FLD Flooded Lead Acid
01 CTM Custom curve
(programmable)
02 YGR Sealed battery curve
03 SLR Sealed battery curve
04 DSG Sealed battery curve
05 SLE Sealed battery curve
08 MAX Opportunity Charge curve
56. NO GASSING The number of hours before
HOURS the charger can begin the
gassing portion of the
charging cycle. (0-8 hours)
57. BATTERY START AMPS
(Opportunity/Fast charging without a BID)
Programs the charger start
rate at the programmed
charger AH setting to the
selected amps/100AH. For
example, to charge an 800AH
battery at 320 amps, the
“battery start amps” would be
programmed to 40A/100AH.
Please note that if the pro-
grammed rate exceeds the
maximum rated charger amps,
the charger output will be
limited to the maximum current
rating.
58. BID START AMPS
(Opportunity/Fast charging with a BID)
Programs the charger start
rate at the programmed BID
AH setting to the selected
amps/100AH. For example,
to charge an 800AH battery
at 320 amps, the “bid start
amps” would be programmed
to 40A/100AH.
Please note
that if the programmed rate
exceeds the maximum rated
charger amps, the charger
output will be limited to the
maximum current rating.
59. MAX CHARGE The maximum battery
TEMP temperature for charging to
start or continue. Once
interrupted, the charge will
restart after the temperature
drops 5 degrees F.
193111-047
SCR2000 CONTROL FEATURES