A01-00159 Rev B
24
15: Charger float voltage setting
Interface
Setting
Parameter 2:
Set up the charger float
voltage.
2.20-2.33:
setting the charger float voltage
from 2.20 V/cell to 2.33V/cell. (Default:
2.28V/cell)
16: EPO logic setting
Interface
Setting
Parameter 2:
Set up the EPO function
control logic.
AO:
Active Open (Default). When AO is
selected as EPO logic, it will activate EPO
function with Pin 1 and Pin 2 in open status.
AC:
Active Close. When AC is selected as
EPO logic, it will activate EPO function with
Pin 1 and Pin 2 in close status.
17: External output isolation transformer connection
Interface
Setting
Parameter 2:
Allow or disallow external
output isolation transformer connection.
ENA:
If selected, it is allowed to connect to
an external output isolation transformer.
DIS:
If selected, it is not allowed to connect
to external output isolation transformer.
(Default)
18: Display setting for autonomy time
Interface
Setting
Parameter 2:
Set up the display setting
for autonomy time
EAT:
If EAT is selected, it will display the
remaining autonomy time. (Default)
RAT:
If RAT is selected, it will show
accumulated autonomy time so far.