Operation
GUPS 2400A
–107 Operation Manual
3-11
3.9.6
Status Words
The status words may be used to examine the current state of the GUPS 2400A-107, but are
not meant to be used in applications that are time
–critical such as AC line loss detection. The
―Line Loss Detected‖ message sent from the GUPS 2400A-107 (refer to Section 3.9.7), or the
AC Line Loss signal (relay contact closure) will have the quickest response time.
3.9.6.1
Status Word 1 Format
Table 3
–5 provides the bit position information and definition of the data in Status Word 1.
Bit
Name
Definition
0
Over Temperature
0 = Normal Operation
1 = Over Temperature
1
Alarm Sense
0 = Alarm Not Sensed
1 = Alarm Sensed
2
Alarm Silence
0 = Alarm Silence Not Enabled
1 = Alarm Silence Enabled
3
Charger Status
0 = Charger Not On
1 = Charger On
4
Current Overload
0 = Normal Operation
1 = Current Overload
5
Battery Switch
0 = Battery Switch Not On
1 = Battery Switch On
6
Test Mode
0 = Normal Operation
1 = Test Mode
7
Inverter Status
0 = Inverter Not On
1 = Inverter On
8
Output Relay
0 = Output Relay Open
1 = Output Relay Closed
9
Impending Shutdown
0 = Greater then 1 minute
1 = Less then 1 minute
10
Rectifier Slow Start
0 = Normal Operation
1 = Rectifier In Slow Start
11
Equalization Charge
0 = Equalization Charge Not On
1= Equalization Charge On
12
Power Available
0 = Power Not Available
1 = Power Available
13
PWM Soft Start
0 = Normal Operation
1 = Unit In Soft Start Mode
14
Reserved
—
15
Battery Slow Start
0 = Normal Operation
1 = Battery Slow Start
Table 3
–5. Status Word 1 Data Format
Содержание GUPS 2400A-107
Страница 2: ......
Страница 4: ...ii This page intentionally left blank...
Страница 13: ...Installation GUPS 2400A 107 Operation Manual 2 3 Figure 2 1 GUPS 2400A 107 Front View...
Страница 14: ...Installation 2 4 GUPS 2400A 107 Operation Manual Figure 2 2 GUPS 2400A 107 Rear View...
Страница 15: ...Installation GUPS 2400A 107 Operation Manual 2 5 Figure 2 3 GUPS 2400A 107 Dimensions Top Side and Front Views...