General Description
1-2
GUPS 2400A
–107 Operation Manual
Battery Recharge Time:
4 hours to 90% full charge following discharge
at 2400VA/1920W and 25°C
Output Voltage:
115V, ±2%
Output Frequency:
60Hz, ±0.1%
Output Current:
20.9A(RMS)
Output Distortion:
2% THD, maximum with linear load
Output Power:
1920W with resistive load;
2400VA/1920W with a reactive load or a non-linear load
Efficiency:
77%
AC to Battery Crossover:
159V, maximum low-line voltage;
232V, minimum high-line voltage
Battery to AC Crossover:
169V, maximum low-line voltage;
232V, minimum high-line voltage
AC Input Voltage Unbalance:
7V (RMS) maximum difference in line voltages
Temperature:
0°C to 40°C (32°F to 104°F), operating;
-40°C to 65°C (-40°F to 149°F), non-operating
Humidity:
5% to 95% non-condensing, operating
Altitude:
0 to 10,000ft, operating;
0 to 40,000ft, 2000ft/min, maximum, non-operating
Dimensions:
7"H x 19"W x 25.1"D,
excluding protrusion of handles, controls, and connectors;
fits standard RETMA rack
Weight:
75lb (34kg), UPS enclosure;
48lb (22kg) battery module;
123lb (56kg) total weight