193111-068
UC2000 CONTROL FEATURES
09. TERM The reason for charge cycle
termination. All possible codes
are listed below:
1-Charge Comp Normal Charge Complete
2-Low Current Low Current Error shutdown
3-Manual Stop Manual stop
4-Battery Dis Battery disconnected while
charging
5-<80 Backup 0-80% Back-up Timer Error
shutdown.
7-Cooling Int CDAC function
8-CDAC Rej CDAC Battery Rejection
9-Curve Error Charger Output Curve Error
shutdown
11-Unbal Line Unbalanced Input Line Error
shutdown
12-Didt Rising Current/Falling Voltage
Error shutdown
13-Lvsd Low Charging Voltage Error
shutdown
14-Ahsd Excessive AH Returned Error
shutdown
15-BID Read BID Error Shutdown
10. EQUALIZE TIME The time of the equalize
portion of the charge cycle.
Equalize can be automatically
or manually selected.
11. START TIME The time at the start of the
charge cycle (AM/PM format).
12. END TIME The time at the end of the
charge cycle. Includes the
equalize time if it was
automatically or manually
selected (AM/PM format).
13. TRUCK I.D. The Truck I.D. number of the
truck that the battery was
discharged in prior to the
charge cycle. Requires
Prestolite Truck and Battery
Identification Modules
(TID and BID).
14. BATTERY I.D. The Battery I.D. number of the
battery that was charged in the
charge cycle. Requires
Prestolite Battery Identification
Module (BID).
15. BATTERY VOLTS The present voltage of the
battery connected to the
battery charger (volts DC).
16. FAN RUN The number of hours
HOURS (k) (thousands) that the charger
fan (if equipped) has run.
17. BID START TEMP The temperature of the battery
sensed by the Prestolite
Battery Identification Module
at the start of the charge cycle
(degrees F).
18. BID END TEMP. The temperature of the battery
sensed by the Prestolite
Battery Identification Module
at the end of the charge cycle
(degrees F).
19. PRESENT TIME
The present time (AM/PM
format).
20. WEEK DAY The present day of week
(SUN through SAT).
21. EQUALIZE TYPE The type of auto equalize
selected. The types that can
be selected are listed below:
CYC. = By cycle count (see
AUTO EQ. COUNT).
D.O.W. = By the day of week
(see Auto EQ. Day).
BID = By BID count
22. EQUALIZE CYCLES The number of charge cycles
between equalize charges
when the auto equalize
function is programmed “ON”
and the auto equalize type is
set to “COUNT”.
23. EQ. DAY The day of the week that an
equalize charge cycle is
performed when the auto
equalize function is “ON”
and the auto equalize type
is set to “DAY”.
24. AUTO EQUALIZE Shows the auto equalize
function on or off.
Auto equalize “OFF”
Auto equalize “ON”
25. T.O.D. START Time of day start time.
(AM/PM). See START MODE.
26. DELAYED START Delayed start time interval.
(00H 00M to 23H 59M).
See START MODE.
7-8 March 31, 2005
Содержание ULTRA CHARGE
Страница 17: ...6 4 March 31 2005 193111 068 OPERATION ULTRA CHARGE RECHARGING CAPABILITY Figure 6 1 ...
Страница 29: ...193111 068 UC2000 CONTROL FEATURES 7 12 Revised October 31 2005 Figure 7 2 ...
Страница 37: ...193111 068 PROGRAMMING YOUR UC2000 CONTROL 8 8 Revised August 30 2005 Figure 8 1 ...
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......