39
A01-00071 Rev F
www.powervar.com
A03-00403 Rev. C
www.powervar.com
Security II Rackmount UPM Specifications
North American 1000 VA Models - Standard
Front Panel Controls
• Power On/Off
• Test
• Load Level LED Gauge
• Battery Charge LED Gauge
• Voltage Manager Boost LED
• Voltage Output On LED
• Voltage Manager Buck LED
• On Battery LED
• Replace Battery LED
• Overload LED
• Fault Code LED
• System Over Temperature LED
Rear Panel Information and Controls
• 6 Foot Power Cord with NEMA 5-15P Plug
• Integrated Switched Power Distribution Unit
(Requires SNMP / Web Card)
•
Configuration Manager DIP Switches
• Communications Manager DB9 Port, USB Port
• Circuit Breaker (AC and DC)
• AC Inlet Module
• Communication Option Slot: SNMP / Web Card, Isolated
Relay Contacts Card, or Remote Off Card
• DC External Battery Cabinet Connector
• Fan (Forced Cooling)
Internal Batteries
• User Hot-Swappable (See Instruction Manual)
• Type: 12 Volt, High Rate 23W
• Quantity: 4 Batteries
• Recharge Time: 6 Hours to 80%, 24 Hours to Full Charge
(For Internal Batteries Only)
Environmental
•
Temperature:
0 - +40℃(32 to 104℉) Operating
-20 to 60℃(-40 to 140℉) Shipment / Storage
• Humidity:
5 to 90% Non-Condensing (Operating,
Shipment/Storage)
• Altitude:
3,000m (10,000 ft) max. Operating;
12,000m (40,000 ft) max. Shipment/Storage
Safety Agency and EMC Compliance:
All Units are Listed by UL and Marked With the UL/cUL Marking
Standard UPM:
Products Listed to:
• UL1778 5th Edition
• CSA 22.2 Nos. 107.3-14
Products in Compliance with:
• FCC-Part 15, Subpart B, Sections 15.107b & 15.109b
Class A Digital Device*
• CISPR11:2009, A1; 2010, Class A*
• IEC61000-4-2, Electrostatic Discharge
• IEC61000-4-3, Radiated Electromagnetic Field Immunity
• IEC61000-4-4, Electrical Fast Transient/Burst Immunity
• IEC61000-4-5, Surge Immunity
• IEC61000-4-6, Immunity to Conducted Radio Frequency
Disturbances
• IEC61000-4-8, Power Frequency Magnetic Field Immunity
• IEC61000-4-11, Voltage Dips, Short Interruptions and
Voltage Variations
*Note: Class B is Available as an Option
Please Consult Your Powervar Sales Representative
RoHS Compliance:
All Products (Standard and Medical) are RoHS Compliant
1000 VA MODELS TYPICAL RUN-TIMES (MINs)
10%
(90W)
20%
(180W)
30%
(270W)
40%
(360W)
50%
(450W)
60%
(540W)
70%
(630W)
80%
(720W)
90%
(810W)
100%
(900W)
Internal Batteries Only
105
52
30
20
15
12
10
8
6
5
In 1) E4804-12
585
292
180
120
90
72
66
53
41
35
In 2) E4804-12
1065
532
330
220
165
132
122
98
76
65
In 3) E4804-12
1545
772
480
320
240
192
178
143
111
95
In 4) E4804-12
2025
1012
630
420
315
252
234
188
146
125
In 5) E4804-12
2505
1252
780
520
390
312
290
233
181
155
In 6) E4804-12
2985
1492
930
620
465
372
346
278
216
185
In 7) E4804-12
3465
1732
1080
720
540
432
402
323
251
215
In 8) E4804-12
3945
1972
1230
820
615
492
458
368
286
245
NOISE REJECTION-ISOLATION:
With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise
output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY:
Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200 amps, 0.5
usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
Warranty/Support:
Powervar warrants the electronics and transformers used in its uninterruptible power managers to be free from defects in materials and work-
manship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment. For service or support on
any Powervar product, please contact Powervar Technical Support at (800) 369-7179 or visit the Powervar website at
www.powervar.com
.
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power,
except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge
cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially
reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and
intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Security II Rackmount UPM Specifications
North American 1000 VA Models - Standard
Содержание ABCE1002-11R 58100-01R
Страница 13: ...13 A01 00071 Rev F www powervar com...