Page 25
User Guide
Plate Mounted Blower Unit
Supplementary Information on Land Purge Blowers
Part no.
Rated
current
Minimum
cable size
Recommended
circuit breaker
Alternative
circuit breaker
PLATE MOUNTED BLOWERS
High Capacity Plate Mounted Blower
110 V 60 Hz Single Phase
099.466
17.4 A
14 awg (2.0 mm
2
)
25 A type C
20 A type D
110 V 50 Hz Single Phase
099.468
11.5 A
14 awg (2.0 mm
2
)
20 A type C
230 V 50 Hz Single Phase
099.465
5.5 A
16 awg (1.5 mm
2
)
10 A type C
220 V 60 Hz Single Phase
099.467
8.7 A
16 awg (1.5 mm
2
)
16 A type C
420 V 50 Hz Three Phase
099.469
2.0 A
16 awg (1.5 mm
2
)
6 A type C
455 V 60 Hz Three Phase
099.470
2.0 A
16 awg (1.5 mm
2
)
6 A type C
Low Capacity Plate Mounted Blower
110 V 60 Hz Single Phase
099.473
7.0 A
16 awg (1.5 mm
2
)
16 A type C
230 V 50 Hz Single Phase
099.471
3.1 A
16 awg (1.5 mm
2
)
10 A type C
220 V 60 Hz Single Phase
099.472
3.5 A
16 awg (1.5 mm
2
)
10 A type C
INTEGRATED BLOWER SYSTEM
High Capacity Blower
110 V 60Hz Single phase
800399
17.4 A
14 awg (2.0 mm
2
)
25 A type C
20 A type D
Low Capacity Blower
110V 60Hz Single Phase
800403
7.0 A
16 awg (1.5 mm
2
)
16 A type C
230V 50Hz Single Phase
800400
3.1 A
16 awg (1.5 mm
2
)
10 A type C
220V 60Hz Single Phase
800401
3.5 A
16 awg (1.5 mm
2
)
10 A type C
During startup, all blower motors draw a surge current which can be several times higher than their running current
Circuit breaker types ‘C’ and ‘D’ refer to the trip characteristics as defined in EN 60 898 and UL 1077