background image

TEST PROCEDURES

TESTING  OF #1 CHECK VALVE

Step 1:  Close #1 and #2 shut off valves.

Step 2:  Open test cocks No. 2, 3, and 4.  Verify that
No. 1 shut off valve is holding tight by observing that
the discharge of water from test cock No. 2 stops.

Step 3:  Attach test kit “Vent” hose to No. 1 test cock;
“Low” hose to No. 2 test cock and “High” hose to No. 3
test cock.  At this point valves (A) and (C) should be
open and (B) should be closed.

Step 4:  Close test cock No. 4.

Step 5:  Open test cock No.1.  The needle of the
differential gauge will indicate a pressure in excess of
15 psi.

Step 6:  Slowly open needle valve (B) until the differen-
tial gauge reads 10 psi.  Then close (B).  The gauge
reading will not change if No. 1 check is holding tight.
If No. 1 check is leaking, the gauge will drop to 0.
Requirements:  The check valve shall be tight against
reverse flow under all pressure differentials.

TESTING  OF #2 CHECK VALVE

Step 1:  Close test cock No. 1.

Step 2:  Open test cock No. 4.

Step 3:  Change “Low” hose from test cock No. 2 to
test cock No. 3.  Change “High” hose from test cock
No. 3 to test cock No. 4.  On the test kit, valves (A) and
(C) should be open and valve (B) should be closed.

Step 4:  Open test cock No. 1.  The pressure differential
gauge will indicate a pressure in excess of 15 psi.

Step 5:  Slowly open needle valve (B) until the gauge
reads 10 psi, then close.  If the gauge reading does not
change, No. 2 check valve is holding tight.  If No. 2
check is leaking, the gauge will drop to 0.

Note in the above testing:  Minor leakage in shut off
valve No. 2 will not affect the test results.  However, in
the testing the No. 1 check, leaking shut off valve No. 1
would cause a good first check to fail the test.

Test Procedure for Double Check Valve Assemblies

using Ames Test Kit

The following Test Procedure is one of several that is recog-
nized throughout the United States for verification of the
functioning of Backflow preventers and is not a specific
recommendation. The Ames test kit is capable of performing
any of the recognized Backflow test procedures.

TROUBLE SHOOTING GUIDE

Symptom

Cause

Solution

1. Check valve fails to hold

a. Debris on check disc

Disassemble and clean

backpressure.

sealing surface

b. Leaking gate valve

Disassemble and clean or repair

c. Damaged seat disc or

Disassemble and replace

seat o-ring

d. Damaged guide holding

Disassemble clean or replace

check open

e. Weak or broken spring

Disassemble and replace spring

2. Chatter during flow

a. Worn, damaged or

Disassemble and repair or

conditions

defective guide

replace guide

3. Low flows passing

a. Mainline check fouled

Disassemble and clean

through mainline
valve (3000 CIV only)

b. Meter strainer plugged

Disassemble and clean

c. Damaged mainline seat

Disassemble and replace

disc or seat

d. Broken mainline spring

Disassemble and replace

RP/IS-2000/3000CIV 0035

EDP# 1915232

Printed in U.S.A.

A

B

C

Vent

High

Low

© Watts Regulator Co., 2000

Содержание 2000 CIV Series

Страница 1: ...llation requirements Limited Warranty Full description of limited warranty is found in Ames Product catalogue This Ames warranty is expressly in lieu of any other warranties ex pressed or implied including without limitation warranties of MER CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Ames shall not be responsible for any incidental or consequential damages including without limitation dama...

Страница 2: ...maintain a continu ous supply of water where interruptions for testing and servicing would be unac ceptable It also has the advantage of pro viding increased capacity where needed beyond that provided by a single valve For two valve installations the total ca pacity of the devices should equal or exceed that required by the system The capacity table below shows the size of the Model 2000CIV 3000CI...

Страница 3: ...V RC4 6 7016308 ARK 2000CIV RC4 8 7016309 ARK 2000CIV RC4 10 Kit includes Disc and Cover o ring Complete Rubber Parts 7016310 ARK 2000CIV RT 21 2 3 7016311 ARK 2000CIV RT 4 7016312 ARK 2000CIV RT 6 7016313 ARK 2000CIV RT 8 7016314 ARK 2000CIV RT 10 Kit includes Two discs and Two cover o rings Seat Kits 7016315 ARK 2000CIV S 21 2 3 7016316 ARK 2000CIV S 4 7016317 ARK 2000CIV S 6 7016318 ARK 2000CIV...

Страница 4: ...reading does not change No 2 check valve is holding tight If No 2 check is leaking the gauge will drop to 0 Note in the above testing Minor leakage in shut off valve No 2 will not affect the test results However in the testing the No 1 check leaking shut off valve No 1 would cause a good first check to fail the test Test Procedure for Double Check Valve Assemblies using Ames Test Kit The following...

Отзывы: