p
Measurement Operation
Note:
Remove plugs from
ends of Test Leads (included)
before connecting to Meter.
Note:
Test Lead probes have removable
covers for overvoltage protection. With
covers in place, Test Leads are rated for
use with CAT III circuits. Exposed probes
are rated for use with CAT II circuits.
Note:
Insert Test Lead into Test Lead Clip
to allow for easier two hand operation.
current Measurement
Measure AC conductors carrying
up to 600 amperes.
WARNING!
To avoid electric shock,
use only one hand to hold Meter
when measuring current.
WARNING!
Remove Test Leads
before taking measurements
with the Current Clamp.
Note:
Amperage is always tested
in series with circuit under test.
Note:
To measure 2- and 3-wire power
cords, use an AC Line Splitter (not included)
and follow its instructions.
1. Turn Rotary Switch to
400-600A~
,
40A~
or
4A~
position. Start with
highest range if amperage is unknown.
2. Using one hand, press Trigger to
open Clamp jaws. Position Clamp
jaws around conductor to be tested.
Guide
Guide
3. Center conductor between guides
in Clamp Jaws, as shown.
4. Read measured current on the Display.
Switch to lower ranges, as necessary,
to get the most accurate reading.
5. When testing is complete, turn
Rotary Switch to
OFF,
and store Meter.