3.0 SYSTEM START-UP
WARNING: This Reverse Osmosis System (RO) contains a preservative solution to
prevent microbiological growth and freezing. Discard all product water for
at least two hours of operation before placing the RO in service.
NOTE: As each component is started and flushed of any debris, make sure to divert
loop water to the drain to flush loop of any debris as well.
For 00SRO1095 RO, refer to Manual 98-0150
For 00MW200 Silex Wall Mount Deionizer, refer to Manual 98-0160
For 00HC-0090-PRV Healthcare Storage Tank, refer to Manual 098-0001
For 0021003 Loop Endotoxin Filter, refer to Manual 98-0033
3.1 OPERATION
Once the system has been started, the SRO will continue to make water until the high-level
float switch is tripped on the storage tank. At this point, the SRO will be placed into standby
(tank full) until the low-level float switch is tripped. Once the low level float is tripped, the
SRO will re-initialize and begin to produce water again. In the event that the TDS is above
the pre-determined set-point, the alarm lamp will light and the HI TDS warning message will
show on the display. This warning will clear when the TDS drops below the Setpoint.