background image

               

             

 

                                                                                                                               

                        98-2024 Rev. A 

 

RAPID RESPONSE WATER SYSTEM 

FOR STERIS 

OPERATION & MAINTENANCE MANUAL 

 

 
 

 
 

Manufactured With Pride 

In The USA 

 

www.ameriwater.com • 800-535-5585 

AmeriWater • 3345 Stop 8 Road • Dayton, OH 45414

Содержание RAPID RESPONSE

Страница 1: ...98 2024 Rev A RAPID RESPONSE WATER SYSTEM FOR STERIS OPERATION MAINTENANCE MANUAL Manufactured With Pride In The USA www ameriwater com 800 535 5585 AmeriWater 3345 Stop 8 Road Dayton OH 45414...

Страница 2: ...98 2024 Rev A...

Страница 3: ...YSTEM INSTALLATION 5 2 1 SRO 5 2 2 WALL MOUNT DI 6 2 3 STORAGE TANK 7 2 4 ENDOTOXIN FILTER 8 3 0 SYSTEM START UP 9 3 1 OPERATION 9 3 2 BYPASS PROCEDURE 10 4 0 MONITORING 11 5 0 PREVENTATIVE MAINTENANC...

Страница 4: ...cation resin bead then an anion then another cation another anion and so on An exchange takes place of course only when a positive ion contacts a negative exchange site and vice versa With each excha...

Страница 5: ...ns Manual before using the system Contact AmeriWater Customer Service with any questions at 1 800 535 5585 Monday through Friday 8 00 a m to 5 00 p m eastern standard time For after hours emergencies...

Страница 6: ...ures and voltage draws please refer to listed component manuals as listed below For 0021003 Loop Endotoxin Filter refer to Manual 98 0033 For 00SRO1095 RO refer to Manual 98 0150 For 00MW200 Silex Wal...

Страница 7: ...4 98 2024 Rev A 1 2 SYSTEM FLOW DIAGRAM Figure 1 1...

Страница 8: ...e wall with anchoring bolts 3 SRO is equipped with sediment and chlorine removal 4 Connect the feed water supply to the inlet 1 2 fitting on the SRO prefilter 5 The feed water supply requires a minimu...

Страница 9: ...ght of the SRO just before the storage tank and within 6 feet from a 120 volt 60 hertz receptacle 2 Assembly should be level when mounted to the wall 3 Connect tubing from the SRO product flow meter o...

Страница 10: ...ansformer into the receptacle and open the inlet and sample port valves 2 3 STORAGE TANK 1 Locate the storage tank on a firm level foundation and anchored securely 2 Connect the Wall Mount DI product...

Страница 11: ...torage tank to the SRO controller and lock in place Figure 2 4 2 4 ENDOTOXIN FILTER 1 Locate and install the Endotoxin Retentive Filter assembly on or near the wall 2 Connect the 3 4 pump discharge ho...

Страница 12: ...8 0160 For 00HC 0090 PRV Healthcare Storage Tank refer to Manual 098 0001 For 0021003 Loop Endotoxin Filter refer to Manual 98 0033 3 1 OPERATION Once the system has been started the SRO will continue...

Страница 13: ...ce your system components Important note If you have a return flow line coming back to the storage tank when using the bypass the returning water from your process will overflow the tank as the distri...

Страница 14: ...uality management system using continuous reading monitors that measure product water quality total dissolved solids These measurements can provide a measure of equipment performance 3 Cartridge filte...

Страница 15: ...PARAMETERS INITIALS Feed Water Temperature 50 F 80 F Feed Water Pressure 20PSI Pump PSI 100 200PSI Product Flow GPM 0 55 0 76 Reject Flow GPM ADJUSTED EQUAL TO PRODUCT Product Quality TDS 25ppm Total...

Страница 16: ...r 20 6001 must be replaced in the event of listed instances below 1 Red light the red light warns that the water conductivity is above the threshold value of 200 000 ohm For 0185 8000 Storage Tank Ven...

Страница 17: ...ees F Gages are located on face plate of the RO and top of the Pre filter housing Return on the Storage Tank and the inlet and outlet of Endotoxin filter Fig 5 1 Step 4 Membranes Remove membranes from...

Страница 18: ...15 98 2024 Rev A Figure 5 1...

Страница 19: ...END CAP 2 25 and 40 SS HSG SMALL BLUE O RING RO Membrane 21 0035 O RING FLTR HOUS 10 SLIMLINE BLUE BLK 50I O NO PR Prefilter Vent Filter and DI 21530233 O RING FLTR HSG 10IN BB SQ THD Loop Endotoxin...