American Standard YK-IOM-2 Скачать руководство пользователя страница 9

9

Gas Pipework Installation
The installation must conform to all standards and regula-
tions. The gas supply pipework and gas stop valve to be in-
stalled near the unit must be dimensioned so as to assure
the gas pressure is sufficient at the unit inlet when operat-
ing at full load.

The pipework must be self supporting and the final connec-
tion to the burner must be made by flexible pipe. Provide a
dust protection (filter) upstream of the unit connection. Look
for gas pipe leaks using "Typo", "1000 bulles" or a similar
product. Soapy water must not be used.

Caution: Never use an open flame to check for gas
leaks. Required gas pressure at the unit inlet
connection are given in Table 4.

Caution: The gas pipework must not exert any
stress on the burner gas connection.

The heating system must be isolated by a gas stop valve
from the gas supply pipe during the pressure test as soon
as it is higher than 0.035 bar. Applying a pressure higher
than 0.035 bar at the unit valve gas could damage it.

Operating Principles of the Gas Heating Module
The heating function of the YK* units is controlled by the
heating module ignition burner. The burner, of the forced air
type, has two capacity stages controlled by the UCP elec-
tronic controller which optimizes the air conditioner opera-
tion.

A normal call for heat is initiated by the UCP, using the tem-
perature detected at the zone sensor. The UCP module in-
ternal relays K5 and K6 energize, which in turn energize
the heat relay (H), the combustion fan motor (CFM), and
the ignition control module (IGN).

The relay K5 switches CFM into high speed. After approxi-
mately 1 minute K5 switches back and the CFM changes
into low speed. If the low pressure fan switch (LPGS), and
the high limit cutout (TC01) are closed, ignition is allowed.
The ignition control module pre-heats the ignition probe (IP)
during approximately 36 seconds. After this pre-heating
stage the gas valve is energized for approximately 8 sec-
onds to ignite the burner. If the burner fails to ignite, the
control module tries again twice before self-locking out.
When the gas ignites successfully, the IP probe is de-ener-
gized and maintains a flame detection function.

If the zone temperature remains below the first stage heat-
ing setpoint for 90 seconds after the heating cycle has
started, the UCP energizes again the K5 relay. The burner
fan then switches into high speed and the heating capacity
is raised to maximum.

When the temperature of the zone has reached the
setpoint, the UCP de-engerizes the relays K5, K6, H and
IGN; the burner then stops.

If the indoor fan is set to auto operation, it will stop 90 sec-
onds after the burner has stopped in order to recover as
much heat as possible from the exchanger.

To reset the ignition controller which has tripped on safety,
it is necessary to cycle power to the unit.

Note: The supply static pressure should be
checked and should be no less than 200 Pa.

In addition to the safety features of the ignition controller, the
burner includes the following safeties:

- detection of a gas supply minimal pressure by the automatic re-

set pressure switch LPGS.

- detection of an abnormal temperature of the supply air (Thermo-

stat TC01).

- detection of an overheating problem due to a lack of air circula-

tion through the heat exchanger (Thermostat TC02).

Table 2 - State of LEDs on Gas-Fired Heating Module

Diagnostics

Green LED Red LED

1. Powered without heating demand

Off

Off

2. Heating demand without fault

Flashing

Off

3. No flame detection on ignition or 

Off

Flashing

   signal detected and then lost
4. Gas unit incorrectly wired or flame 

On

Flashing

    signal detected on a heating demand
5. Internal fault

Off

On

Putting the Gas-Fired Heating Module into Operation
(Reserved for the qualified gas technician)

 This type of burner can only

be put into operation by an approved techician who has
read the following procedure beforehand, or preferably
has undergone the training course on Trane gas burners.

Before performing ignition tests it is first necessary to perform the
following operations:

- Check if gate valve is present
- Check if an expansion valve is present. This valve must be
   adapted to the type of gas used:
* G 20 : 20 mb
* G 25 : 25 mb
* G 31 : 37 or 50 mb

Note: To operate with propane gas, the burner is fitted
with a limiter (supplied by Trane).

- Vent the gas line
- Check the gas pipe is leak-tight upstream of the gas unit (see
drawing). Use Typol or a foaming product ("1000 bulles" aerosol or
similar). Do not use soapy water.

- Check the pressure upstream of the gas unit (the pressure con-

nection is located on the minimum gas pressure cut-out). This
cut-out must be set to 15 mbar. This operation must be carried
out while the burner is not operating.

- Check voltage at the TNS2 transformer output:

- 115 volts for power supply of the IGN module (L1 - L2 and S1 -

S2).

   230 volts for power supply of the burner fan motor.

Содержание YK-IOM-2

Страница 1: ...ould be done by qualified experienced technicians American Standard Inc 2000 Voyager TM Packaged Gas Electric 085 thru 250 Units INSTALLATION OPERATION MAINTENANCE Customer Property Contains wiring se...

Страница 2: ...nstallation 14 Evaporator Fan Adjustment 14 Compressors 16 Pre Start Quick Check List 19 Power up Initialization 20 Unitary Control Processor UCP 20 Manifold Pressure 20 Final Installation Checklist 2...

Страница 3: ...perature sensing function to the UCP Ignition Control Module There are two LED s located in the Ignition Control Module that monitor the operating status of the heater during the vari ous operating st...

Страница 4: ...and control will revert to the zone sensor To terminate the test mode cycle the unit power at the unit disconnect Resistance Test Mode The resistance test mode is initiated by applying the appropri a...

Страница 5: ...r Horizontal HORIZONTAL UNIT SI mm REAR VIEW SHOWING DUCT OPENINGS FOR HORIZONTAL AIR FLOW UNITS A B C D E F YK 085C 100C 406 413 510 76 162 914 YK 100B 125C 571 457 437 51 100 1053 YK 155B 175C 673 4...

Страница 6: ...59 1509 2267 51 357 25 205 1205 1A YK 155B 175C 1692 1600 46 530 435 724 2588 1702 2597 51 357 25 191 1410 1A YK 200B 250B 2048 1956 46 565 591 725 2969 2057 2977 51 357 25 191 1765 Figure 1B Curb Dim...

Страница 7: ...low or Horizontal Note Corner weights are given for information only Unit is to be supported continuously by curb or equivalent frame support Unit Support If unit is to be roof mounted check building...

Страница 8: ...o closer than two feet from the unit to minimize noise and resistance Attaching Horizontal Ductwork to Unit All conditioned air ductwork should be insulated to mini mize heating and cooling duct losse...

Страница 9: ...e K5 relay The burner fan then switches into high speed and the heating capacity is raised to maximum When the temperature of the zone has reached the setpoint the UCP de engerizes the relays K5 K6 H...

Страница 10: ...10 Figure 5 Figure 6 Detail of the Gas Section...

Страница 11: ...h due to electrical shock or contact with moving parts Measure the negative pressure downstream of the gas unit Connect a flexible hose to the gas unit branch connection and connect as electronic pres...

Страница 12: ...onditioner 50 Hz EEC Voyager G20 41 4 92 49 1 91 70 6 90 77 4 91 G25 35 0 92 38 3 89 59 4 88 60 3 90 G31 37 7 92 48 6 90 57 3 88 78 2 92 YK 063CD X YK 073CD X YK 073DD X YK 085CD X YK 089CD X YK 100CD...

Страница 13: ...Gas Flow 15 C 1013 mbar m3 h 4 7 5 3 8 3 8 2 Heat Rate kW 38 0 43 0 67 4 67 0 Reduce Rate Gas Flow 15 C 1013 mbar m3 h 4 5 4 9 7 8 7 9 Heat Rate kW 36 5 40 0 63 4 64 0 Natural Gas G31 30 37ou 50 mbar...

Страница 14: ...AND ADJUSTED IF REQUIRED TO A NEGATIVE 50Pa 0 2 OF WATER COLUMN NEVER ADJUST THE REGULATOR TO A POSITIVE PRESSURE Manifold Pressure The unit manifold pressure regulator located on the gas valve is fa...

Страница 15: ...cor dance with national and local codes Power Wiring The power supply lines must be run in weather tight conduit to the disconnect and into the bottom of the unit control box Provide strain relief for...

Страница 16: ...ow 1 2 3 etc Connections should be made using 1 to 1 2 to 2 3 to 3 and so on See following example Zone Temperature Sensor Terminal Strip Terminal Terminal I D 1 ZTEMP 2 SIGNAL COMMON 3 CSP 4 MODE 5 H...

Страница 17: ...17 Figure 11A Zone Sensor Interconnections...

Страница 18: ...18 Figure 11B Conventional Thermostat Interconnections...

Страница 19: ...plying unit After all electrical wiring is complete SET THE ZONE SEN SOR SWITCH TO THE OFF POSITION AND THE FAN SWITCH TO AUTO SO COMPRESSOR AND FAN WILL NOT RUN and apply power by closing the system...

Страница 20: ...lock out Reset by disconnecting and re applying unit power Unit will start in the high fire mode After a short run cycle it will switch to low fire Note Blue smoke produced by the heat exchanger durin...

Страница 21: ...this unit from the roof use the Test mode procedure on page 3 and 4 of this manual Operating Pressures After the unit has operated in the cooling mode for a short pe riod of time install pressure gaug...

Страница 22: ...ons warrant Examine these areas of unit 1 Filters for cleaning or replacement 2 Motors and drive system components 3 Economizer gaskets for possible replacement 4 Condenser coils for cleaning 5 Safety...

Страница 23: ...23...

Страница 24: ...24...

Отзывы: