American Standard YK-IOM-2 Скачать руководство пользователя страница 11

11

4. Reconnect the sensor and re-ignite the burner. Once the

burner is ignited, simulate a high temperature failure by dis-
connecting a wire from the sensor TC01. The gas valve
should close and stop the flaem, re-connect TC01. The ig-
nition sequence will be initiated. The burner should re-light
after about 45 seconds.

5. Once the burner is ignited, simulate overheating by discon-

necting a wire from the sensor TC02. This stops all the
burner's elements (fan and gas valve should no longer be
energized). Reconnect the TC02 wire.

Adaption to available gases (See Table 3)
The gas-fired heating modules built into YK* units are avail-
able in different categories. The units are supplied ready to
operate using natural gases G20 (20 mbar) and G25 (25
mbar) or using gas  G31 (37 mbar).

The transition from G20 gas to G25 gas does not require any
action. The available power in G25 gas supply is reduced.

The transition from G20 to G31 gas requires the following
modifications.
- Change of the gas intake orifice in the burner's fan.
- Implementation of pressure limiter.

 The orifice and the limiter

for supply with gas G31 must be manufactured by
Trane.

.
Start up
Operating check list before the start-up
- Unit is level, with sufficient clearance all around.
- Duct network is correctly dimensioned according to the unit

configuration, insulated and water tight.

- Condensate drainage line is correctly dimensioned, equipped

with trap and sloped.

- Filters are in position: correct size and quantity, clean.
- Wiring is correctly sized, and connected in accordance with

wiring diagrams.

- Power supply lines are protected by recommended fuses

and correctly earthed.

- Thermostat is correctly wired and positioned unit is checked

for refrigerant charge and leaks.

- Indoor and outdoor fans rotate freely and are fixed on shafts.
- Indoor fan rotation speed is set.
- Access panels and doors are replaced to prevent air entering

and risks of injury.

- Checking of the gas heating section, in accordance with

above precedure.

 If any operating checks

must be performed with the unit operating, it is the
technician's responsibility to recognize any possible
hazards and proceed in a safe manner. Failure to do
so could result in severe personal injury or death due
to electrical shock or contact with moving parts.

- Measure the negative pressure downstream of the gas unit.

Connect a flexible hose to the gas unit branch connection
and connect as electronic pressure gauge, or failing this a
U tube.

- Start the burner by modifying the thermostat's set point or by

using the "test mode" terninals on the machines terminal
strip.

- Measure the downstream partial vacuum. It must be between

- (minus) 5 mm and  - (minus) 9 mm of water head.

- Check the supply pressure upstream of the gas unit once

more when it is operating to ensure the pressure has not
dropped.

Important note: In the event this measurement is
correct, do not adjust the gas unit setting. It has been
set in the factory.

When the measured partial vacuum is positive (above
atmospheric pressure)
- Remove the paint mark on the brass threaded plug with two

holes drilled in it, located on the gas unit, and unscrew it
(See Figure 6).

- To increase the partial vacuum turn the screw counter-clock-

wise.

- Measure the partial vacuum again while the burner is operat-

ing.

- When the adjustment is finished, seal the brass threaded

plug with paint.

It is highly recommended to check the combustion gases with
a flue gas analyzer. The measured valves must be within the
following ranges:
-Carbon monoxide (CO) less than 50 PPM
-Oxygen (O2) greater than 1.5%
-Carbon dioxide (CO2) less than 11%

Note: If the correct setting cannot be obtained,
contact the Trane technicians.

Checking the correct operation of the burner
After having iginited the burner a few times, it is necessary to
check the proper operation of the burner safeties by following
the following procedure:

1. Close the main gas valve, and then simulate a demand for

heating. The burner must start, and then stop when the
quantity of gas contained in the pipe between the main
valve and the built-in gas unit has run out. To ensure this
takes place, following the drop in supply pressure, the
LPGS cut-out must open and stop all the gas supply chain
components (fans, gas valve, ignition controller). Any at-
tempt to ignite the system again must fail.

2. Open the main gas valve. The pressure switch LPGS

should automatically reset. The burner can now be put
back into operation.

3. Ignite the burner. Once it is burning, simulate a flame failure

by disconnecting a wire of the flame detection sensor
(quick connect). The ignition controller should immediately
stop the burner and close the gas valve.

Содержание YK-IOM-2

Страница 1: ...ould be done by qualified experienced technicians American Standard Inc 2000 Voyager TM Packaged Gas Electric 085 thru 250 Units INSTALLATION OPERATION MAINTENANCE Customer Property Contains wiring se...

Страница 2: ...nstallation 14 Evaporator Fan Adjustment 14 Compressors 16 Pre Start Quick Check List 19 Power up Initialization 20 Unitary Control Processor UCP 20 Manifold Pressure 20 Final Installation Checklist 2...

Страница 3: ...perature sensing function to the UCP Ignition Control Module There are two LED s located in the Ignition Control Module that monitor the operating status of the heater during the vari ous operating st...

Страница 4: ...and control will revert to the zone sensor To terminate the test mode cycle the unit power at the unit disconnect Resistance Test Mode The resistance test mode is initiated by applying the appropri a...

Страница 5: ...r Horizontal HORIZONTAL UNIT SI mm REAR VIEW SHOWING DUCT OPENINGS FOR HORIZONTAL AIR FLOW UNITS A B C D E F YK 085C 100C 406 413 510 76 162 914 YK 100B 125C 571 457 437 51 100 1053 YK 155B 175C 673 4...

Страница 6: ...59 1509 2267 51 357 25 205 1205 1A YK 155B 175C 1692 1600 46 530 435 724 2588 1702 2597 51 357 25 191 1410 1A YK 200B 250B 2048 1956 46 565 591 725 2969 2057 2977 51 357 25 191 1765 Figure 1B Curb Dim...

Страница 7: ...low or Horizontal Note Corner weights are given for information only Unit is to be supported continuously by curb or equivalent frame support Unit Support If unit is to be roof mounted check building...

Страница 8: ...o closer than two feet from the unit to minimize noise and resistance Attaching Horizontal Ductwork to Unit All conditioned air ductwork should be insulated to mini mize heating and cooling duct losse...

Страница 9: ...e K5 relay The burner fan then switches into high speed and the heating capacity is raised to maximum When the temperature of the zone has reached the setpoint the UCP de engerizes the relays K5 K6 H...

Страница 10: ...10 Figure 5 Figure 6 Detail of the Gas Section...

Страница 11: ...h due to electrical shock or contact with moving parts Measure the negative pressure downstream of the gas unit Connect a flexible hose to the gas unit branch connection and connect as electronic pres...

Страница 12: ...onditioner 50 Hz EEC Voyager G20 41 4 92 49 1 91 70 6 90 77 4 91 G25 35 0 92 38 3 89 59 4 88 60 3 90 G31 37 7 92 48 6 90 57 3 88 78 2 92 YK 063CD X YK 073CD X YK 073DD X YK 085CD X YK 089CD X YK 100CD...

Страница 13: ...Gas Flow 15 C 1013 mbar m3 h 4 7 5 3 8 3 8 2 Heat Rate kW 38 0 43 0 67 4 67 0 Reduce Rate Gas Flow 15 C 1013 mbar m3 h 4 5 4 9 7 8 7 9 Heat Rate kW 36 5 40 0 63 4 64 0 Natural Gas G31 30 37ou 50 mbar...

Страница 14: ...AND ADJUSTED IF REQUIRED TO A NEGATIVE 50Pa 0 2 OF WATER COLUMN NEVER ADJUST THE REGULATOR TO A POSITIVE PRESSURE Manifold Pressure The unit manifold pressure regulator located on the gas valve is fa...

Страница 15: ...cor dance with national and local codes Power Wiring The power supply lines must be run in weather tight conduit to the disconnect and into the bottom of the unit control box Provide strain relief for...

Страница 16: ...ow 1 2 3 etc Connections should be made using 1 to 1 2 to 2 3 to 3 and so on See following example Zone Temperature Sensor Terminal Strip Terminal Terminal I D 1 ZTEMP 2 SIGNAL COMMON 3 CSP 4 MODE 5 H...

Страница 17: ...17 Figure 11A Zone Sensor Interconnections...

Страница 18: ...18 Figure 11B Conventional Thermostat Interconnections...

Страница 19: ...plying unit After all electrical wiring is complete SET THE ZONE SEN SOR SWITCH TO THE OFF POSITION AND THE FAN SWITCH TO AUTO SO COMPRESSOR AND FAN WILL NOT RUN and apply power by closing the system...

Страница 20: ...lock out Reset by disconnecting and re applying unit power Unit will start in the high fire mode After a short run cycle it will switch to low fire Note Blue smoke produced by the heat exchanger durin...

Страница 21: ...this unit from the roof use the Test mode procedure on page 3 and 4 of this manual Operating Pressures After the unit has operated in the cooling mode for a short pe riod of time install pressure gaug...

Страница 22: ...ons warrant Examine these areas of unit 1 Filters for cleaning or replacement 2 Motors and drive system components 3 Economizer gaskets for possible replacement 4 Condenser coils for cleaning 5 Safety...

Страница 23: ...23...

Страница 24: ...24...

Отзывы: