American Standard YK-IOM-2 Скачать руководство пользователя страница 19

19

Diagram Improper Electrical Phase Sequence

Proper compressor motor electrical phasing can be quickly de-
termined and corrected before starting the unit. Use a quality
instrument such as an Associated Research Model 45 Phase
Sequence Indicator and follow this procedure.

1. Open the electrical disconnect or circuit protection switch

that provides line power to the High Voltage Terminal Block
(HTB1) in the control panel.

2. Connect the phase sequence indicator leads to the HTB1

as follows:

Phase Seq. Lead

HTB1 Terminal

Black (Phase A)

L1

Red (Phase B)

L2

Yellow (Phase C)

L3

 Bodily injury can result

from high voltage electrical components. If operating
checks must be performed with the unit operating, it
is the technician’s responsibility to recognize these
hazards and proceed safely. Failure to do so could
result in severe personal injury or death due to
electrical shock or contact with moving parts.

3 . Read the phase sequence on the indicator after turning
power on by closing the unit disconnect switch. The “ABC” in-
dicator on the face of the phase indicator will glow if phase is
ABC.

4. If the “CBA” indicator glows instead, open the unit main dis-
connect and interchange any two main line leads on HTB1. re-
close the unit main disconnect and recheck phasing.

5. Open units main disconnect before continuing with installa-
tion.

6. Disconnect the phase indicator.

 Open and lock unit

disconnect switch before continuing installation.
Failure to do so could result in severe personal injury
or death due to electrical shock or contact with
moving parts.

Note:  If a phase indicator is not available, follow the
electrical phasing sequence in the cooling start-up
section to insure proper compressor rotation.

IMPORTANT: After completion of wiring, check all
electrical connections, including factory wiring within
the unit, and ensure all connections are tight. Replace
and secure all electrical box covers and access doors
before leaving unit or connecting power to circuit
supplying unit.

After all electrical wiring is complete, SET THE ZONE SEN-
SOR SWITCH TO THE OFF POSITION AND THE FAN
SWITCH TO AUTO SO COMPRESSOR AND FAN WILL NOT
RUN, and apply power by closing the system main disconnect
switch. This will activate the compressor crankcase heaters.

Do not change the zone sensor setting until power has been
applied long enough to evaporate any liquid refrigerant in the
compressor. It is recommended the crankcase heaters be en-
ergized for 8 hours prior to starting.

Exception -  Both circuits on the125 thru 250 units are not
equipped with crankcase heaters.

Start-Up
Pre-Start Quick Check List

[ ]  Is unit properly located and level with proper clearances?

See Figure 1A and 1B.

[ ]  Is the duct work correctly sized, run, taped, insulated and

weather proofed with proper unit arrangement? (See duct
work installation)

[ ]  Is the gas piping correctly sized, run, and purged of air?

(See gas piping)

[ ]  Is condensate line properly sized, run, trapped and

pitched?

[ ]  Is the filter of the correct size and number, clean and in

place?

[ ]  Is the wiring properly sized and run in according to the unit

wiring diagram?

[ ]  Are all wiring connections tight including those in unit and

compressor electrical boxes?

[ ]  Has the unit been properly grounded and fused with the

recommended fuse size? (see wiring data)

[ ]  Is the zone temperature sensor correctly wired and in a

good location?

[ ]  Have the air conditioning systems been checked at the

service ports for charge and leak tested if necessary?

[ ]  Does the condenser fan and indoor blower turn freely

without rubbing and are they tight on the shafts?

[ ]  Has the indoor blower speed been determined and the

proper speed been set? (See air flow performance data)

[ ]  Has all work been done in accordance with applicable local

and national codes?

[ ]  Are all covers and access panels in place to prevent air

loss and safety hazards?

 Bodily injury can result

from high voltage electrical components. If operating
checks must be performed with the unit operating, it
is the technician’s responsibility to recognize these
hazards and proceed safely. Failure to do so could
result in severe personal injury or death due to
electrical shock or contact with moving parts.

Содержание YK-IOM-2

Страница 1: ...ould be done by qualified experienced technicians American Standard Inc 2000 Voyager TM Packaged Gas Electric 085 thru 250 Units INSTALLATION OPERATION MAINTENANCE Customer Property Contains wiring se...

Страница 2: ...nstallation 14 Evaporator Fan Adjustment 14 Compressors 16 Pre Start Quick Check List 19 Power up Initialization 20 Unitary Control Processor UCP 20 Manifold Pressure 20 Final Installation Checklist 2...

Страница 3: ...perature sensing function to the UCP Ignition Control Module There are two LED s located in the Ignition Control Module that monitor the operating status of the heater during the vari ous operating st...

Страница 4: ...and control will revert to the zone sensor To terminate the test mode cycle the unit power at the unit disconnect Resistance Test Mode The resistance test mode is initiated by applying the appropri a...

Страница 5: ...r Horizontal HORIZONTAL UNIT SI mm REAR VIEW SHOWING DUCT OPENINGS FOR HORIZONTAL AIR FLOW UNITS A B C D E F YK 085C 100C 406 413 510 76 162 914 YK 100B 125C 571 457 437 51 100 1053 YK 155B 175C 673 4...

Страница 6: ...59 1509 2267 51 357 25 205 1205 1A YK 155B 175C 1692 1600 46 530 435 724 2588 1702 2597 51 357 25 191 1410 1A YK 200B 250B 2048 1956 46 565 591 725 2969 2057 2977 51 357 25 191 1765 Figure 1B Curb Dim...

Страница 7: ...low or Horizontal Note Corner weights are given for information only Unit is to be supported continuously by curb or equivalent frame support Unit Support If unit is to be roof mounted check building...

Страница 8: ...o closer than two feet from the unit to minimize noise and resistance Attaching Horizontal Ductwork to Unit All conditioned air ductwork should be insulated to mini mize heating and cooling duct losse...

Страница 9: ...e K5 relay The burner fan then switches into high speed and the heating capacity is raised to maximum When the temperature of the zone has reached the setpoint the UCP de engerizes the relays K5 K6 H...

Страница 10: ...10 Figure 5 Figure 6 Detail of the Gas Section...

Страница 11: ...h due to electrical shock or contact with moving parts Measure the negative pressure downstream of the gas unit Connect a flexible hose to the gas unit branch connection and connect as electronic pres...

Страница 12: ...onditioner 50 Hz EEC Voyager G20 41 4 92 49 1 91 70 6 90 77 4 91 G25 35 0 92 38 3 89 59 4 88 60 3 90 G31 37 7 92 48 6 90 57 3 88 78 2 92 YK 063CD X YK 073CD X YK 073DD X YK 085CD X YK 089CD X YK 100CD...

Страница 13: ...Gas Flow 15 C 1013 mbar m3 h 4 7 5 3 8 3 8 2 Heat Rate kW 38 0 43 0 67 4 67 0 Reduce Rate Gas Flow 15 C 1013 mbar m3 h 4 5 4 9 7 8 7 9 Heat Rate kW 36 5 40 0 63 4 64 0 Natural Gas G31 30 37ou 50 mbar...

Страница 14: ...AND ADJUSTED IF REQUIRED TO A NEGATIVE 50Pa 0 2 OF WATER COLUMN NEVER ADJUST THE REGULATOR TO A POSITIVE PRESSURE Manifold Pressure The unit manifold pressure regulator located on the gas valve is fa...

Страница 15: ...cor dance with national and local codes Power Wiring The power supply lines must be run in weather tight conduit to the disconnect and into the bottom of the unit control box Provide strain relief for...

Страница 16: ...ow 1 2 3 etc Connections should be made using 1 to 1 2 to 2 3 to 3 and so on See following example Zone Temperature Sensor Terminal Strip Terminal Terminal I D 1 ZTEMP 2 SIGNAL COMMON 3 CSP 4 MODE 5 H...

Страница 17: ...17 Figure 11A Zone Sensor Interconnections...

Страница 18: ...18 Figure 11B Conventional Thermostat Interconnections...

Страница 19: ...plying unit After all electrical wiring is complete SET THE ZONE SEN SOR SWITCH TO THE OFF POSITION AND THE FAN SWITCH TO AUTO SO COMPRESSOR AND FAN WILL NOT RUN and apply power by closing the system...

Страница 20: ...lock out Reset by disconnecting and re applying unit power Unit will start in the high fire mode After a short run cycle it will switch to low fire Note Blue smoke produced by the heat exchanger durin...

Страница 21: ...this unit from the roof use the Test mode procedure on page 3 and 4 of this manual Operating Pressures After the unit has operated in the cooling mode for a short pe riod of time install pressure gaug...

Страница 22: ...ons warrant Examine these areas of unit 1 Filters for cleaning or replacement 2 Motors and drive system components 3 Economizer gaskets for possible replacement 4 Condenser coils for cleaning 5 Safety...

Страница 23: ...23...

Страница 24: ...24...

Отзывы: