American Standard Standard Residential Скачать руководство пользователя страница 7

4

Important air for combustion and ventilation must not come from a 

corrosive atmosphere. Any failure due to corrosive elements in the 

atmosphere is exclude from warranty coverage.

The following types of installation 

(not limited to the following) 

will require 

outdoor air for combustion due to chemical exposure and may reduce 

but not eliminate the presence of corrosive chemicals in the air.

•  Beauty shops.

•  Photo processing labs. 

•  Buildings with indoor pools. 

•  Water heaters installed in laundry, lobby, or craft rooms.

•  Water heaters installed in chemical storage areas.

 Combustion air must be free of acid-forming chemicals such as 

sulfur, fluorinem chlorine. These elements are found in aerosol sprays, 

detergents, bleaches, cleaning solvents, air fresheners, paint and varnish 

removers, refrigerants, and many other commercial or household 

products. When burned, vapors from these products form highly 

corrosive acid compounds. These products should not be stored or 

used near water heater or air inlet.

Combustion and ventilation air requirementes are determined by the 

location of the water heater. The water heater may be located in either 

an open 

(unconfined) 

area or in a confined area or small enclosure, such as 

a closet or small room. Confined spaces are areas with less than 50 sq. 

ft.

ALL AIR

 

FROM 

INSIDE THE 

BUILDING

The confined space shall be provided with two permanent openings 

communicating directly with an additional room(s) of sufficient volume 

so that the combined volume of all spaces meets the criteria for an 

unconfined space shall be considered in making this determination. Each 

opening shall hace a minimum free area of 1 square inch pero 1,000 

BTU per hour of the total input rating of all gas utilization equipment in 

the confined space, but not less than 100 square inches.

The confined space shall be provided with 

two permanent openings, one commencing 

within 12 inches of the top and one 

commencing within 12 inches of the 

bottom of the enclosure. The openings shall 

communicate directly, or by ducts, with the 

outdoors or space 

(crawl or attic) 

that freely 

communicate with the outdoors.

When directly communicating with the 

outdoors, each opening shall have a minimum 

free area of 1 square inch per 4,000 BTU per 

hour of total input rating of all equipment in 

the enclosure. 

(Figure 6)

When communicating with the outdoors 

through vertical ducts, each openings shall 

have a minimum free area of 1 square per 

inch per 4,000 BTU per hour of total input 

rating of all equipment in the enclosure. 

(Figure 7)

1. When communicating with the outdoors 

through horizontal ducts, each duct opening 

shall have a minimum free area of 1 square 

inch per 2,000 BTU per hour of total input 

rating of all equipment in the enclosure.

(Figure 8)

When ducts are used, the shall be of the 

same cross-sectional area as the free area 

of the openings to which they connect. The 

minimum dimension of rectangular air ducts 

shall not be less than 3 inches. For other 

combustion and ventilation air openings, 

refer to the National Fuel Gas Code ANSI 

Z223.1.*

Water

Heater

12" MAX

CHIMNEY OF GASVENT

12" MAX

MIN

MIN

AIR DUCT

100 sq in

100 sq in

Opening

Fig. 5

AIR SUPPLY

ALL AIR  

FROM 

OUTDOORS

ONE OPENING SHALL BE WITHIN 
12 INCHES OF THE TOP AND ONE 
WITHING 12 INCHES OF THE BOTTOM 
OF THE  ENCLOSURE.

VENTILATION

LOUVERS

(EACH END OF ATTIC)

VENTILATION

LOUVERS

(EACH END OF ATTIC)

ALT. INLET

AIR

AIR OUTLET

AIR OUTLET

WATER HEATER

WATER HEATER

FURNACE

FURNACE

INLET AIR DUCT

INLET FT AIR 

DUCT

ENDS 1”

ABOVE FLOOR

VENTILATION LOUVERS

Содержание Standard Residential

Страница 1: ...valve for the correct gas DO NOT USE THIS WATER HEATER WITH ANY GAS OTHER THAN THE ONE LISTED ON THE DATA PLATE Failure to use the correct gas can cause problems which can result in DEATH SERIOUS BOD...

Страница 2: ...operation Be alert for thermal expansion Refer to instruction manual for installation and service Water temperature over 125 F 52 C can cause severe burns instantly resulting in severe injury or deat...

Страница 3: ...ce replacement instructions 25 Burner maintenance replacement 26 Draining and flushing interior of tank Venting system inspection tampering 27 Emergency shutdown condensation smoke odor L P and natura...

Страница 4: ...service technician Water heaters subjected to flood conditions or anytime the gas controls main burner or pilot have been submerged in water require replacement of the entire water heater American Gas...

Страница 5: ...ame vicinity or area containing or gas water heater or other flammable or spark producing appliance Do not locate the water heater near an air moving device The operation of air moving devices such as...

Страница 6: ...CAP OR PLUG THE END AIR GAT 6 MINIMUM CAP DRIP LEG SEDIMENT TRAP MINIMUM LENGHT 3 DRAIN LINE SHOULD BEAT LEAST 3 4 IN AND PITCHED FOR PROPER DRAINAGE TO AN OPEN DRAIN DRAIN PAN MUST LIMIT WATER ACCUM...

Страница 7: ...1 000 BTU per hour of the total input rating of all gas utilization equipment in the confined space but not less than 100 square inches The confined space shall be provided with two permanent openings...

Страница 8: ...r heater must be properly vented for the removal of exhaust gases to the outside atmosphere Correct installation of the vent pipes system is mandatory for the proper and efficient operation of this wa...

Страница 9: ...er of this water heater recommends installing a thermostatic mixing valve or an anti scald device in the domestic hot water line These valves reduce the point of use temperature of the water by mixing...

Страница 10: ...temperature and pressure relief valve and discharge line 5 Must terminate at an adequate drain 6 Must not have any valve between the relief valve and the heater Failure to maintain the properly liste...

Страница 11: ...ure it is fully seated around the cold water pipe Also ensure that the base of insulation is flush with the water heater Once seated secure the insulation with a section of tape SPACE HEATING POTABLE...

Страница 12: ...r control or temperature and pressure relief valve Tampering with any of these componets is DANGEROUS and can result in property damage or severe injury Tampering avoids all warranties Only qualified...

Страница 13: ...the center line of the terminal 12 in L above paved sidewalk or paved driveway located on public property 7 ft E to unventilated soffit 12 in M under veranda porch deck or balcony 12 in F to outside...

Страница 14: ...ith the heater The power cord supplied may be used on a unit only where local codes permit If local codes do not permit use of flexible power supply cord a Make sure the unit is unplugged from the wal...

Страница 15: ...eater must be vented separately from all other appliances The unit may be vented horizontally through a wall or vertically through the roof Pipe runs must be adequately supported along both vertical a...

Страница 16: ...ent temperature and humidity of installation location ambient temperature and humidity of venting space vent discharge and slope and product usage In certain conditions installations in unconditioned...

Страница 17: ...of condensate from the flue gases can develop Provision must be made for the condensate to drain freely from the system or to be collected in a condensate trap s that can be drained Damage or fracture...

Страница 18: ...ipe for various elbows using Schedule 40 PVC CPVC and polypropylene Vent Pipe Size Elbow Type Short Sweep Short Radius Long Sweep Long Radius Notes 1 Use long radius elbows where possible Minimum dist...

Страница 19: ...alues shown in Table 1 6 Measure the vent piping and cut to required lengths Pipes must be cut at right angles and deburred to ensure a good smooth fit with sufficient overlap for the glue joints Corr...

Страница 20: ...nnections must be properly seated and tightened to prevent the leakage of flue gases into the area See Figure 19 through Figure 22 2 The water heater is supplied with a 3 x 2 rubber coupling to accept...

Страница 21: ...ON OF MATERIALS PCV and CPVC VENTING Cutting Device Saw or Pipe Cutter Deburring Tool Knife File or Beveling Machine 2 and above Brush Pure Bristle Rag Cotton Not Synthetic Primer and Cleaner Solvent...

Страница 22: ...uantity of cement must be applied to the joint to fill the gap between the pipe and fitting The gap must be filled to obtain a strong leak free joint D Inspection cleaning priming Visually inspect the...

Страница 23: ...ill soft The joint should not be disturbed immediately after the cementing procedure and sufficient time should be allowed for proper curing of the joint Exact drying time is difficult to predict beca...

Страница 24: ...e latest edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 Horizontal piping slopes at an upward pitch of 1 8 in rise per 4 ft away from the water heater Not obstructed in any way Venting properly...

Страница 25: ...anufacturer of this heater will not be liable for incidents arising or resulting from the use of external insulation blankets The manufacturer will not be liable for corrosion of the parts which may h...

Страница 26: ...swich on the right side of the gas valve down to the OFF position 6 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety in...

Страница 27: ...resistant to the action of liquefied petroleum L P gases Apply pipe dope sparingly to the male threads only DO NOT apply pipe dope to the gas valve The water heater and its individual gas shut off val...

Страница 28: ...e electronig gas valve thermostat do not use pipe wrench or vise the grip body Do not insert any pipe of blunt instrument into the inlet or outlet connections Use these type tools may result in damage...

Страница 29: ...ior door with the top seal 9 Turn the gas valve on and make sure all connections are tight and no gas smell is present Then light on the heater according to the aperating instructions Once the burner...

Страница 30: ...with a vacuum cleaner by vacuuming both the top and bottom surfaces When reinstalling the burner assembly make sure all gasket material is positioned properly If any of the gasket are damaged the heat...

Страница 31: ...ondition During the summer months the warmer incoming water temperatures will benefit the performance of your water heater and reduce the amount of condensation developed Condesation does not mean tha...

Страница 32: ...the condensation will stop Operting the warer heater at the lowest electronic valve temperature setting can keep the water heater in the condensation mode Adjusting the electronic valve setting slight...

Страница 33: ...installed at least one anode rod see Parts section for protection of the tank Certain water conditions will cause a reaction between this rod and the water This is defined as smelly water and removal...

Страница 34: ...LAINTS ARE DUE TO ITEMS NOT DIRECTLY RELATED TO THE WATER HEATER DO NOT ATTEMPT TO SERVICE THE WATER HEATER OF PERFORM OTHER RECOMMENDATIONS ON THIS LIST UNLESSYOU ARE TRAINED AND QUALIFIED TO DO SO V...

Страница 35: ...th correct orifice see rating plate 3 Turn temperature knob to higher setting 4 Refer to gas control error codes 5 Drain flush provide water treatment if needed 6 Install adequate heater 7 Correct pip...

Страница 36: ...NG AND CARBON FORMATION 1 Air inlets blocked 2 Insufficient air 3 Low gas pressure 4 Orifice too large 5 Flue clogged 6 Defective gas control valve 7 Heater installed in a confined are 8 Burner flame...

Страница 37: ...eplace High limit switch HOT SURFACE IGNITER NOT GLOWING FOLLOWING WARM UP PERIOD 1 I20VAC polarity reversed at 120VAC outlet receptable 2 Defective hot surface igniter 3 Defective gas control valve 4...

Страница 38: ...when the main controller fails and must be replaced The gas control valve includes a temperature limiting ECO Energy Cut Off system that will shut off the water heater if the water temperature is too...

Страница 39: ...Limit Lockout thermostat temperature limit was exceeded Five Flash three second pause Flame Out Of Sequence Six One Flash three second pause Soft Lockout Retry Limit Failed Trial For Ignition Six Two...

Страница 40: ...th pipes was not 6 exceeded 7 Ensure there are no obstructions in the exhaust and air intake pipes 8 If there are excessive restrictions in the air intake pipe the air pressure switch N C will open 9...

Страница 41: ...uctions in the exhaust and air intake pipes 7 If there are excessive restrictions in the air intake pipe the air pressure switch N C will open 8 Check air pressure switch performance Check blower vacu...

Страница 42: ...CE 15 FV SENSOR 16 VAPOR SENSOR BRACKET 17 HARNESS SENSOR FVR AND TOD NOT SHOWN 18 EXTERIOR DOOR 19 ELECTRICAL SWITCH ITEM PARTS DESCRIPTION REPAIR PARTS ILLUSTRATION LEGEND A Special anode rod see pa...

Страница 43: ...40...

Страница 44: ...ne directory commercial listings or local utility for qualified service assistance 2 Should your problem not be solved to your complete satisfaction you should then contact the Manufacturer s Service...

Отзывы: