M9097

ENTHALPY CHANGEOVER
SETPOINT

LED LIGHTS WHEN
OUTDOOR AIR IS SUITABLE 
FOR FREE COOLING

INSERT DC MILLIAMMETER BETWEEN SO AND S FOR CHECKOUT 

AND TROUBLESHOOTING.

JUMPER USED FOR SINGLE ENTHALPY CONTROL.

TR

TR1

A

B

C

D

SO

SR

+

+

+

C7400

620 OHM
JUMPER

DC 
MILLIMETER

W7459

S

+

1

1

M9098B

ENTHALPY
CHANGEOVER
SETPOINT

MINIMUM 
DAMPER
POSITION 
SETTING

LED LIGHTS
WHEN OUTDOOR 
AIR IS SUITABLE 
FOR FREE COOLING

MINIMUM DAMPER POSITION ADJUSTMENT 
IS PRESENT ONLY ON W7459A,D MODELS. 

Meter Location for Checkout and Troubleshooting

Location of Enthalpy Set Point, Minimum Posi-
tion and LED

Table 2. Enthalpy Checkout Procedure

Figure 13.  Enthalpy LEDs and Checkout

Checkout Procedure

 Response

A

1. Disconnect power at TR and TR1.

2. Disconnect jumper P to P1.

3. Jumper TR to 1.

4. Jumper T1 to T.

5. If connected, remove C7400 Solid State Enthalpy Sensor

from teminals S0 and +. Ensure factory-installed 620 ohm

resistor is connected to terminals Sr and +.

6. Apply power (24Vac) to terminals TR and TR1

LED is off.
Motor is in closed position.

B

1. Disconnect factory-installed 620 ohm resistor from

terminals Sr and +.

Led turns on,  motor drives toward open.

C

1. To simulate high and low enthalpy (single enthalpy

sensor) reconnect factory-installed 620 ohm resistor from
termonals Sr and +. Connect 1.2K ohm 4074EJM Checkout

Resistor across terminals So and +.

__

2. Turn enthalpy setpoint potentiometer to "A".

LED turns on, indicating low enthalpy.
Motor drives toward open.

3. Turn enthalpy setpoint potentiometer to "D".

LED turns off, indicating high enthalpy.
Motor drives toward closed.

4. Disconnect the 1.2 K ohm checkout resistor.

__

D

1. To verify sensor operation, reconnect the + lead of the

outdoor enthalpy sensor to the + terminal of W7459.

__

2 Connect a DC millimeter between terminal So of the
W7459A and terminal S of the enthalpy sensor. See Fig. 10

(positive meter lead to terminal S of the enthalpy sensor).

Millimeter indication is between 3 and 25
mA if sensor is operating properly.
If millimeter indicates zero, the sensor may
be wired backward.

3. When using differential enthalpy, check the return air
enthalpy sensor by connecting a DC millimeter between
terminal Sr of the W7459A and terminal S of the return air
enthalpy sensor.  (positve meter lead to terminal S of the
enthalpy sensor).

Millimeter indication is between 3 and 25
mA if sensor is operating properly.
If millimeter indicates zero, the sensor may
be wired backward.

Содержание BAYECON101A

Страница 1: ...cessible through the Coil access panel Important The Economizer installation requires that you first install an air filter rack ordered separately Use BAYFLTR101A for 2 4YC WC TC DC 018 3036A BAYFLTR2...

Страница 2: ...TC WC or YC Unit Horizontal Return Air Panel Down Flow Return Air Panel Blower Access Panel Control Box Access Panel Coil Access Panel Mixed Air Sensor Economizer Assembly Rainhood Assembly Mist Elimi...

Страница 3: ...ptions at this time per instructions provided 6 Route Main Wiring 1 From the Economizer assembly pass the wire harness through the coil grommet See Figure 10 view A on page 7 Continue routing the harn...

Страница 4: ...ert Assembly screw 1 Swing Down Return Air Damper Return Air Damper 3 Tighten Linkage rod Figure 6 Start Economizer s Front Mounting Screws Economizer outline Install two 2 screws into holes Leave ext...

Страница 5: ...izer rain hood Figure 7 Mounting Rain Hood Top flange of hood slides under HVAC unit s top sealing flange HVAC unit s top sealing flange Hood HVAC unit 2 Drive six 6 self tapping screws into the keyho...

Страница 6: ...0 2 82 View A Approximate Mounting Dimension See View A Return Duct Roofcurb Relief damper Mist eliminator filter Economizer rain hood Outside air dampers Return air dampers Required filter kit order...

Страница 7: ...outing Behind Compressor Compartment and into Blower Compart ment 3 Pull the two 2 Mixed Air Sensor Wires with female quick connects from the Harness and Route Down Near the Mixed Air Sensor Connect t...

Страница 8: ...PAGE 8 INSTALLER S GUIDE Figure 11 TC YC Economizer Connection Diagram...

Страница 9: ...PAGE 9 INSTALLER S GUIDE Figure 12 WC Economizer Connection Diagram...

Страница 10: ...set screws This motor checkout ensures that 1 The motor operates the load 2 The motor responds properly to the controller 3 There is no binding of the linkage or motor stalling at any point of travel...

Страница 11: ...s Sr and Led turns on motor drives toward open C 1 To simulate high and low enthalpy single enthalpy sensor reconnect factory installed 620 ohm resistor from termonals Sr and Connect 1 2K ohm 4074EJM...

Страница 12: ...Inc 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement It reserves the right to change design and specification without notice 200...

Отзывы: