PAGE 10

INSTALLER’S GUIDE

5.  Checkout

SINGLE ENTHALPY CHANGEOVER SET POINT

Single enthalpy:

 The enthalpy

changeover set point is set to return the
outdoor air damper to minimum posi-
tion when the enthalpy rises above its
set point. The enthalpy set point scale
markings, located on W7459, are
A,B,C,D; see table

 

for the correspond-

ing control point. The factory-installed
R4 WHITE 620-ohm jumper must be in
place across ter and SR.

Operate the motor through its complete open-close stroke. If
necessary, release one of the previously tightened linkage con-
nections to prevent damage. Check for proper operation, making
sure that the linkage does not bind and that the motor travels
smoothly throughout its fully open and closed position. Table 1
describes how to drive the motor to the full open and full closed
positions (power connected). If there is excess length of linkage
rod, cut it to size. Make necessary minor adjustments until
desired operation is obtained, and tighten all nuts and set screws.
This motor checkout ensures that:

1. The motor operates the load.

2. The motor responds properly to the controller.

3. There is no binding of the linkage or motor stalling at any

point of travel.

If motor does not operate properly, check for proper voltage or
mechanical binding in linkage or damper.

If questions arise regarding this product, contact your distributor
or representative.

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX.  F ( C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12      14      16      18      20      22      24      26      28      30      32      34      36      38      40      42     

 44      46

90

100

80

70

60

50

40

30

20

10

ENTHALPY—BTU PER POUND DRY AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

APPROXIMATE DRY BULB TEMPERATURE— F ( C)

A

A

B

B

C

C

D

D

M11681

RELATIVE HUMIDITY (%)

1

1

HIGH LIMIT CURVE FOR W7459D.

MODEL

DRIVE MOTOR OPEN

DRIVE MOTOR CLOSED

SPRING RETURN

M7415

Power  to TR and TR1, jumper T and T1.

Disconnect jumper at T or T1 and

disconnect P or P1,if connected.

Disconnect power at TR and TR1.

Table 1. Motor Operation Checkout

Содержание BAYECON101A

Страница 1: ...cessible through the Coil access panel Important The Economizer installation requires that you first install an air filter rack ordered separately Use BAYFLTR101A for 2 4YC WC TC DC 018 3036A BAYFLTR2...

Страница 2: ...TC WC or YC Unit Horizontal Return Air Panel Down Flow Return Air Panel Blower Access Panel Control Box Access Panel Coil Access Panel Mixed Air Sensor Economizer Assembly Rainhood Assembly Mist Elimi...

Страница 3: ...ptions at this time per instructions provided 6 Route Main Wiring 1 From the Economizer assembly pass the wire harness through the coil grommet See Figure 10 view A on page 7 Continue routing the harn...

Страница 4: ...ert Assembly screw 1 Swing Down Return Air Damper Return Air Damper 3 Tighten Linkage rod Figure 6 Start Economizer s Front Mounting Screws Economizer outline Install two 2 screws into holes Leave ext...

Страница 5: ...izer rain hood Figure 7 Mounting Rain Hood Top flange of hood slides under HVAC unit s top sealing flange HVAC unit s top sealing flange Hood HVAC unit 2 Drive six 6 self tapping screws into the keyho...

Страница 6: ...0 2 82 View A Approximate Mounting Dimension See View A Return Duct Roofcurb Relief damper Mist eliminator filter Economizer rain hood Outside air dampers Return air dampers Required filter kit order...

Страница 7: ...outing Behind Compressor Compartment and into Blower Compart ment 3 Pull the two 2 Mixed Air Sensor Wires with female quick connects from the Harness and Route Down Near the Mixed Air Sensor Connect t...

Страница 8: ...PAGE 8 INSTALLER S GUIDE Figure 11 TC YC Economizer Connection Diagram...

Страница 9: ...PAGE 9 INSTALLER S GUIDE Figure 12 WC Economizer Connection Diagram...

Страница 10: ...set screws This motor checkout ensures that 1 The motor operates the load 2 The motor responds properly to the controller 3 There is no binding of the linkage or motor stalling at any point of travel...

Страница 11: ...s Sr and Led turns on motor drives toward open C 1 To simulate high and low enthalpy single enthalpy sensor reconnect factory installed 620 ohm resistor from termonals Sr and Connect 1 2K ohm 4074EJM...

Страница 12: ...Inc 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement It reserves the right to change design and specification without notice 200...

Отзывы: