Installation Guide

18  

 11-HD15D1-5-EN

6.5  Stage Thresholds

The threshold to allow operation is a Load Value greater 
than 5 and operation is always terminated with a Load 
Value less than 1. 
Load Value also determines when additional stages of 
operation are requested. To prevent rapid cycling between 
stages, a stage threshold is enforced. The stage threshold 
is dependent on the applied system.

LV=100

LV=200

STAGE 2

COMPRESSOR STAGING THRESHOLDS

100-115

100-115

100-125

100-125

100-110

100-110

Y1  to Y2 

Y1  to Y2 

HP to W1

HP to W1

HP to Dual Fuel

HP to Dual Fuel

ST

A

GE 3

ST

A

GE 1

LV=100

LV=200

LV=300

LV=400

ST

A

GE 5

ST

A

GE 1

STAGE 2

STAGE 3

STAGE 4

AUX ELECTRIC HEAT - STAGING THRESHOLDS

100-

115

100-

115

200-

215

200-

215

300-

315

300-

315

W1 to W2

W1 to W2

W2 to W3

W2 to W3

Compressor to W1

Compressor to W1

LV=100

LV=200

LV=300

ST

A

GE 4

ST

A

GE 1

STAGE 2

STAGE 3

AUX FOSSIL HEAT - STAGING THRESHOLDS

100-

125

100-

125

175-

190

175-

190

175-

190

175-

190

Inhibit - Compressor to W1

Inhibit - Compressor to W1

W1 to W2

W1 to W2

W2 to W3

W2 to W3

LV=100

LV=200

LV=300

ST

A

GE 4

ST

A

GE 1

STAGE 2

STAGE 3

AUX WET HEAT - STAGING THRESHOLDS

100-

125

100-

125

200-

215

200-

215

Compressor to W1

Compressor to W1

W1 to W2

W1 to W2

6.6  Stage Inhibits

When the stage threshold is exceeded, a stage inhibit is 
applied. The stage inhibit calculates the rate of recovery 
over a 10-minute period and determines if the next stage is 
required to meet the current demand. If the rate of recovery 
is great enough, a new 10-minute inhibit is enabled. The 
1050 Control will not go to the next stage of operation until it 
determines that the current stage cannot satisfy the current 
demand. Stage inhibits only apply between compressor 
stages and compressor heat to indoor heat. Stage inhibits 
do not apply to indoor heat stages. 
Stage inhibits can be disabled in the 1050 Control 
Installer Setup>Comfort Settings.

START INHIBIT

10 Minutes

Y1 “ON”

Y2 “ON”

Y1 “ON”

LV = 100

LOAD VALUE (LV)

LV = 110

Stage Inhibits - Compressor Staging

Stage Inhibits - Compressor to Aux Heat

START INHIBIT

10 Minutes

Y1 “ON”

W1 “ON”

W1 “OFF”

LV = 100

LOAD VALUE (LV)

LV = 115

START INHIBIT

10 Minutes

Y1 “ON”

W1 “ON”

Y1 “ON”

45 Second

Cool Down

LV = 100

LOAD VALUE (LV)

LV = 125

Stage Inhibits - Duel Fuel

Note: Stage Thresholds do not apply to Variable Speed 
Outdoor Unit operation.

Note: Stage Inhibits do not apply to Variable Speed 
Outdoor Unit operation.

Содержание AZON1050AC52ZA

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furth...

Страница 2: ...rk Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 8 5 1 Power Up Sequence 8 5 2 Guided Setup Wizards 8 5 3 Installer Setup Screens 8 5 3 1 Group 1 Stan...

Страница 3: ...minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized 2 Product Specifications 3 General Information...

Страница 4: ...from the Internet router Tips to Help Maximize Signal Strength Mount the 1050 Control within 30 feet of wireless router Install 1050 Control with no more than three interior walls between it and the...

Страница 5: ...ires extend through the Sub base See Figure 3 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4 of insulation from...

Страница 6: ...nel B C R D ODT ODT RS RS R B D R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL INDOOR UNIT 1050 COMFORT CONTROL Heat Pump Multi Stage AC Caution Do not run Outdoor Remote sensor wire...

Страница 7: ...unicating Controls w S9V2 Furnace and Comm Outdoor B C R D ODT ODT RS RS R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL S9V2 FURNACE OUTDOOR UNIT 1050 COMFORT CONTROL Caution Do not...

Страница 8: ...ower Type Non Variable Variable Select the indoor blower type Constant Torque motors are considered non variable speed All Group 1 settings will be auto configured for fully communicating systems 5 Sy...

Страница 9: ...when a voting zone is also requesting capacity Indoor Heating Airflow Offset above and below cooling airflow 1 50 50 0 The air flow offset is the difference between the design cooling air flow CFM per...

Страница 10: ...a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A...

Страница 11: ...uring 1st stage indoor heat operation 2nd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 Select of cycles per hour during 2nd stage indoor heat operation 3rd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 S...

Страница 12: ...lect whether an outdoor temperature override is allowed Outdoor temperature sensor must be connected and enabled to allow this setting to be selected Ventilator Fan Action Ventilate with Blower Ventil...

Страница 13: ...r cooling mode with a setpoint change greater than 2 Heating Aggressive Recovery 2 by Outdoor Temperature Enable Disable Select whether the 10 minute staging inhibit is disabled during heating mode wh...

Страница 14: ...ower On Delay for variable speed blowers only 1 minute at 50 7 5 minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating...

Страница 15: ...Disable Enable Enable defrost heater balance point for W3 only applicable when indoor heat is electric or hydronic Defrost Heater Balance Point W3 Setting 5 F 45 F Select an outdoor temperature to di...

Страница 16: ...ler Code When an 1050 Control is connected to Nexia a Dealer Code can be entered to auto populate the dealer s contact information and logo The code is the dealer s registered phone number listed on A...

Страница 17: ...Stage Gas Oil Heat LOAD VALUE RANGE COOLING 0 100 Single Stage Compressor 0 200 Two Stage VSPD Compressor A Load Value of 50 represents a request of 50 demand for single stage cooling units Y or 50 de...

Страница 18: ...AGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 6 Stage Inhibits When the stage threshold is exceeded a stage inhibit is app...

Страница 19: ...igured to only limit Day operation only limit Night operation or limit Day and Night operation to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Q...

Страница 20: ...ort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 1050 Control has the ability to control a Whole House Dehumidifier through the normally open dry AUX Contacts on the optional...

Страница 21: ...SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lockout Once enabled select an outdoor temperature which disables auxiliary heat anytime the outdoo...

Страница 22: ...ilation only The ventilation run time per hour can be adjusted to meet ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the...

Страница 23: ...default setting Trane or American Standard manufactured indoor unit with a variable speed blower branded Geothermal package units and oil furnaces are not supported Field supplied 24 volt transformer...

Страница 24: ...on for each same mode calling zone follows the calculation below Zone LV System LV damper position The minimum opening position is always 25 to reduce air whistling from a partially opened damper Zone...

Страница 25: ...odels If the 1050 Control still calculates excess air then the excess will be relieved following the rules below Relief Strategy 1 Divide the excess air evenly between the zones which are calling but...

Страница 26: ...rect compressor speed and associated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must...

Страница 27: ...ll is not immediately required Alert messages are not displayed on the home screen NORMAL Functionality may be lost but should recover or the information is for diagnostic purposes performance monitor...

Страница 28: ...or speed currently operating Cool Current cooling set point per zone Load Value Numerical value used to determine how much capacity is required to meet set point For more information see 6 2 Load Valu...

Страница 29: ...uipment 3 Check repair system Heating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is no...

Страница 30: ...time of inactivity Screen Saver mode set to Black which turns of screen back light after a user selected time of inactivity Normal operation User may change screen saver from Black to Indoor Temperat...

Страница 31: ...l interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following me...

Страница 32: ...D1 5 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: